10kV Metal Oxide Surge Arrester (ZnO Diverter) - Reliable Protection by China Factory & Suppliers
Core Applications
In 10kV power systems, it is mainly used for lightning overvoltage protection, effectively safeguarding system insulation and conductors from the damaging effects of lightning. Meanwhile, it can also suppress switching overvoltages, transient overvoltages, etc., and is widely suitable for overvoltage protection of substations, distribution lines, switchgear, transformers, and other equipment, playing a key role in insulation coordination of 10kV power networks.
Technical Advantages and Features
I. Gapless Design, Safe & Reliable
It abandons the gap structure of traditional arresters, completely eliminating the risk of sparkover and system shock when gaps break down. There is no need for an additional voltage grading system, making the structure simpler and reliability significantly improved.
II. Extremely Low Leakage Current
During normal operation, the leakage current of ZnO varistors is much lower than that of other diverters, reducing the equipment's own energy consumption and heat generation, and enhancing long-term operation stability.
III. No Power Follow Current
There is no power follow current after operation, avoiding secondary impact on equipment and systems, and greatly simplifying protection logic.
IV. High Energy Absorption Capacity
It has excellent energy absorption capacity and can effectively deal with high-energy overvoltage impacts such as lightning strikes and switching overvoltages.
V. Excellent Long-Term Stability
It maintains high stability during and after prolonged discharge, ensuring continuous and reliable operation of the equipment under complex working conditions.
VI. Dynamic Overvoltage Control
In addition to suppressing switching overvoltages, it can also effectively control dynamic overvoltages, helping 10kV systems achieve economically reasonable insulation coordination and reducing overall construction and operation and maintenance costs.
Typical Technical Parameters (Taking Mainstream 10kV Models as Examples)
Taking two typical 10kV metal oxide surge arresters, YH5WS-17/50 and YH5WZ-17/45, as examples, their technical parameters are as follows:
| Type | System Rated Voltage (kV) | Rated Voltage (kV r.m.s) | Continuous Operating Voltage (kV r.m.s) | DC Reference Voltage (kV) | 2ms Square Wave Current (A) | Residual Voltage(≤kVp) | Continuous Current Resistance Component mA(peak) | ||
|---|---|---|---|---|---|---|---|---|---|
| 30/60μs Steep Impulse | 8/20μs Lightening Impulse | 1/10μs Operating Impulse | |||||||
| YH5WS-17/50 | 10 | 17 | 13.6 | 25 | 100 | 57.5 | 50 | 42.5 | 0.2 |
| YH5WZ-17/45 | 10 | 17 | 13.6 | 24 | 200 | 51.8 | 45 | 38.3 | 0.2 |
With its outstanding technical advantages and precise parameter design, the metal oxide surge arrester has become the preferred solution for overvoltage protection in 10kV power systems, building a solid defense for the safe and efficient operation of the power grid.
Frequently Asked Questions (FAQs)
They are mainly used for lightning overvoltage protection in 10kV power systems to protect system insulation and conductors. They are widely applied in substations, distribution lines, switchgear, and transformers to manage switching and transient overvoltages.
The gapless design completely eliminates the risks of sparkover and system shock associated with gap breakdown. It does not require an additional voltage grading system, which simplifies the structure and significantly increases operational reliability.
During normal operation, the leakage current of ZnO varistors is extremely low. This minimizes the arrester's own energy consumption and heat generation, leading to enhanced long-term stability.
Having no power follow current after operation prevents secondary electrical impacts on the protected equipment and system, which greatly simplifies the overall system protection logic.
While both share a 10kV system rated voltage, 17kV rated voltage, and 13.6kV continuous operating voltage, they differ in capacity. The YH5WS-17/50 has a 2ms square wave current of 100A and a lightning impulse residual voltage of 50kV, whereas the YH5WZ-17/45 supports a 200A square wave current and features a lower lightning impulse residual voltage of 45kV.