China BKRM6-40.5 SF6 Gas-Insulated Ring Main Unit Suppliers | High-Quality Factory Switchgear
Overview
BKRM6-40.5 metal ring network switchgear (hereinafter referred to as the inflatable cabinet) is suitable for use in three-phase AC 50Hz, rated voltage 40.5kV distribution systems. It is used for breaking and closing load currents, overload currents, overload currents, and short circuits. It can also disconnect capacitive loads such as no-load transformers, overhead lines at a certain distance, cable lines, and capacitor banks. It plays a role in the distribution, control, and protection of electrical energy in the power system.
BKRM6-40.5 adopts a fully sealed structure, and all primary charged components are sealed in a stainless steel welded chamber with a protection level of IP67. A multi circuit ring network switchgear that can adapt to various harsh environmental conditions such as humidity, salt spray, floods, heavy pollution, etc., and has high operational safety and reliability. Widely used in industrial parks, streets, airports, residential areas, bustling commercial centers, etc., it is an ideal equipment for distribution network automation. It is also used for compact box type substations, cable branch boxes, switch stations, wind power stations, subway and tunnel lights.
BKRM6-40.5 has multiple modules that can be combined according to user requirements, providing multiple combination methods to adapt to the vast majority of situations that require ring network units. Up to 4 modules can be configured in the same SF6 gas chamber. When there are more than 4 units in the module, an extended busbar can be used to connect the switchgear.
Key Advantages
Fully Sealed & Insulated
All live parts are sealed in a 304 stainless steel box filled with SF6 gas (1.4 bar, IP67 protection). Perfect for high humidity, dust, mines, and polluted areas. Uses DIN47636 standard conduits and fully shielded cable joints.
High Safety & Reliability
Passed internal fault arc test of 20kA/0.5s. Features a reliable pressure relief channel. Three-position load and grounding switches simplify interlocking, preventing accidental entry into live intervals.
Maintenance-Free & Long Lifespan
Designed for a 30-year operational lifespan during which the main switch requires no maintenance. The annual gas leakage rate is kept strictly at ≤ 0.1%.
Compact Structure
Except for air-insulated metering and PT cabinets, all modules are only 500mm wide. Consistent ground height for cable connection sleeves simplifies on-site construction.
Intelligent Control
Can be equipped with optional intelligent control devices, providing effective protection, remote control, and monitoring systems to support distribution automation.
Dual Protection Options
Offers load switch fuse combinations for transformers of 1600kVA and below, and circuit breakers with relay protection for transformers of various capacities.
Environmental Protection
Developed with eco-friendly processes and zero-leakage cleaning technology. Sealed for life, with 90% to 95% of materials fully recyclable after its life cycle.
Product Parameters
Item |
Unit |
C Module |
F Module |
V Module |
CB Module |
||
(Load Switch) |
(Combined Apparatus) |
(Vacuum Switch) |
Isolation/ |
(Vacuum Circuit Breaker) |
Isolation/ |
||
Rated Voltage |
kV |
36/40.5 |
35/40.5 |
36/40.5 |
36/40.5 |
36/40.5 |
36/40.5 |
Power Frequency Withstand Voltage |
kV |
70/95 |
70/95 |
70/95 |
70/95 |
70/95 |
70/95 |
Isolation Port Voltage |
kV |
80/110 |
80/110 |
80/110 |
|
|
80/110 |
Lightning Impulse Withstand Voltage (Isolation Port) |
kV |
170/185 |
170/185 |
170/185 |
170/185 |
170/185 |
170/185 |
Isolation Port (kV) |
kV |
195/215 |
|
195/215 |
|
|
195/215 |
Rated Current |
A |
630/6301 |
|
200/200 |
|
630/630 |
|
Breaking Capability |
|
|
|
|
|
|
|
Active Load |
A |
630/6330 |
|
200/200 |
|
|
|
Loop Current Breaking |
A |
630/630 |
|
200/200 |
|
|
|
NoLoad Cable Charging |
A |
20/21 |
|
20/21 |
|
50(C1) |
|
Ground Fault |
A |
60/63 |
|
60/63 |
|
|
|
Ground Fault Cable Charging |
A |
35/36 |
|
35/36 |
|
|
|
Transfer Current |
A |
|
|
840/750 |
|
|
|
ShortCircuit Breaking Current |
kA |
|
|
20(Expected) |
|
20/20[EI,S] |
|
Making Capacity |
kA |
50/50 |
|
|
|
|
|
(50 Times) |
50/50 |
|
|
|
|
|
|
(50 Times) |
50(Expected) |
2.5/2.5 |
|
|
|
|
|
(5 Times) |
50/50 |
50/50 |
|
|
|
|
|
Class (Electrical Life) |
|
E3/E2 |
E2/E2 |
/ |
E2/E2 |
E2/E2 |
E2/E2 |
3s ShortTime Withstand Current |
kA |
20/20 |
20/20 |
Limited by HighVoltage Fuse |
|
20/20 |
20/20 |
Internal Arc Classification IAC AFL. 1s |
|
20/20 |
|
20/20 |
|
20/20 |
|
Frequently Asked Questions
The BKRM6-40.5 switchgear is designed for three-phase AC 50Hz distribution systems with a rated voltage of 40.5kV. It is used to distribute, control, and protect electrical energy by breaking and closing load, overload, and short-circuit currents.
It utilizes a fully sealed structure where all primary charged components are protected inside a 304 stainless steel welded chamber with an IP67 protection rating. This design allows it to adapt to harsh environments like humidity, salt spray, floods, and heavy pollution.
The BKRM6-40.5 has a designed lifespan of 30 years, during which the main switch is completely maintenance-free. Its annual SF6 gas leakage rate is exceptionally low at ≤ 0.1%.
It offers two main protection methods: a load switch fuse combination (typically for transformers rated at 1600kVA and below) and vacuum circuit breakers paired with relay protection (suitable for transformers of various capacities).