China FLRN36-12D SF6 High Voltage Load Switch - Reliable Suppliers and Factory Solutions for 10kV Power Systems
Overview
The FLRN36 - 12D SF₆ high - voltage load switch is an indoor switchgear applicable to three - phase AC 10kV, 50Hz power systems. It uses SF₆ gas as the arc - extinguishing and insulating medium, integrating three functions of closing, opening, and grounding into one unit, and is sealed in an epoxy resin shell filled with SF₆ gas, featuring a compact structure. It has characteristics such as reliable interlocking, high insulation strength of fracture ports, and maintenance - free operation. It can be matched with complete sets of power distribution equipment, ring - main switch cabinets, etc., and is used in scenarios like urban network renovation and industrial and mining enterprises to realize power distribution, control, and protection. Moreover, it can be adapted to intelligent units to achieve “three remotes” (remote control, remote signaling, remote measurement). It has a fast fault - breaking speed, which is beneficial for system stability.
Product Features
Efficient Arc - Extinguishing & Insulation
Leverages SF₆ gas for strong arc - quenching and stable insulation, ensuring high - strength fracture port insulation per GB 3906.
Integrated Functionality
Combines closing, opening, and grounding in one compact epoxy - resin - sealed unit, simplifying cabinet layout.
Reliable Interlocking
Mechanical/electrical interlocks prevent misoperations, aligning with DL/T 534 for safe grid operation.
Maintenance - Free Design
Sealed SF₆ system avoids regular refilling, reducing lifecycle costs.
Smart Compatibility
Pairs with intelligent units for “three remotes” (control, signaling, measurement), enabling digital grid integration.
Fast Fault Handling
Rapid fault interruption stabilizes systems, ideal for urban networks/industrial applications per GB/T 11022.
Product Parameters
| No. | Item | Unit | Data |
|---|---|---|---|
| 1 | Rated voltage | KV | 12 |
| 2 | Rated frequency | Hz | 50 |
| 3 | Rated current | A | 630 |
| 4 | Rated peak withstand current | KA | 50 |
| 5 | 4s rated short time withstand current | KA | 20 |
| 6 | Rated making current | KA | 50 |
| 7 | Rated breaking current - Active load breaking current | A | 630 |
| Rated breaking current - Breaking current loop | A | 630 | |
| Rated breaking current - Cable charging breaking current | A | 10 | |
| 8 | 1min power frequency withstand voltage (phase to phase, to earth, fracture) | KV | 42/48 |
| 9 | Lightning impulse withstand voltage (phase to phase, to earth, fracture) | KV | 75/85 |
| 10 | Relative pressure of SF6 gas (20℃ GP) | MPa | ≤0.04 |
| 11 | Rated operating voltage (electric) | V | AC220、DC220 |
| 12 | Rated voltage of shunt release | V | AC220、DC220 |
| 13 | Average opening speed | m/s | 3.5±1.5 |
| 14 | Average closing speed | m/s | 3.5±1.5 |
| 15 | Three - phase points, closing phase of the same | ms | ≤3 |
| 16 | The main circuit resistance | μΩ | ≤120 |
| 17 | Manual maximum torque | N.m | ≤160 |
| 18 | phase to phase center distance | mm | 210±0.5 |
Frequently Asked Questions (FAQ)
What is the main application of the FLRN36-12D load switch?
It is an indoor switchgear designed for three-phase AC 10kV, 50Hz power systems, widely used in urban network renovations, industrial and mining enterprises, and ring-main switch cabinets to achieve power distribution, control, and protection.
What medium does this switch use for arc-extinguishing and insulation?
The switch utilizes SF₆ (sulfur hexafluoride) gas as the arc-extinguishing and insulating medium, which is securely sealed inside a compact epoxy resin shell.
Does the FLRN36-12D require regular gas refilling or maintenance?
No. It features a sealed-for-life SF₆ system and a maintenance-free design, which eliminates the need for regular gas refilling and substantially lowers overall lifecycle costs.
Can this load switch be used in smart grid installations?
Yes, it is highly compatible with intelligent units to enable "three remotes" functions: remote control, remote signaling, and remote measurement.
What safety mechanisms are built into this load switch?
It integrates closing, opening, and grounding functions with reliable mechanical and electrical interlocks to prevent misoperations, ensuring safe grid operations in compliance with DL/T 534 standards.
What is the rated voltage and current capacity of the FLRN36-12D?
It has a rated voltage of 12 kV, a rated frequency of 50 Hz, and a rated current of 630 A, making it highly suitable for standard 10kV power distribution networks.