The FZN25 - 12 T type indoor high - voltage AC vacuum load switches and the FZRN25 - 12D type indoor high - voltage AC vacuum load switch - fuse combination appliances are control and protection devices for three - phase AC 50Hz, 12kV power distribution systems. The products are oil - free, non - toxic, and free from fire and explosion hazards, and are widely used in industrial and mining enterprises, urban building substations and other places. The latter has more reliable protection for electrical equipment such as transformers than circuit breakers, and is especially suitable for ring network, dual - radial power supply units and compact substations.
The FZN25 - 12 type indoor high - voltage AC vacuum load switch (hereinafter referred to as the load switch) is an indoor device with three - phase AC 50Hz and rated voltage 12kV, suitable for industrial and mining enterprise distribution substations and power stations and other places. It serves as protection and control for electrical facilities, and is used for breaking load current, loop current, no - load transformers and cable charging current. It has the ability to close short - circuit current. Its opening and closing operation mechanism can be manual and electric, facilitating the realization of three - remote control requirements for the power system.
The FZN25 - 12 type indoor high - voltage AC vacuum load switch - fuse combination appliance (hereinafter referred to as the combination appliance) is an indoor device with three - phase AC 50Hz and rated voltage 12kV, suitable for industrial and mining enterprise distribution substations and power stations and other places. It is used for load control and short - circuit protection. It also has an earthing switch with the ability to close short - circuit current. Its operating mechanism can be manual and electric, facilitating the realization of three - remote control requirements for the power system.
Main Technical Parameters
| No. | Item | Unit | FZN25 - 12/T630/20 | FZRN25 - 12D/T200/31.5 |
|---|---|---|---|---|
| - | Product Type | - | FZN25 - 12/T630/20 | FZRN25 - 12D/T200/31.5 |
| 1 | Rated Voltage | kV | 12 | 12 |
| 2 | Rated Current | A | 630 | 200 |
| 3 | Rated Frequency | Hz | 50 | 50 |
| 4 | Rated Insulation Level | |||
| - | 1min Power - Frequency Withstand Voltage | kV | Interrupter fracture: 30; To ground, phase - to - phase: 42; Isolation fracture: 48 |
Interrupter fracture: 30; To ground, phase - to - phase: 42; Isolation fracture: 48 |
| - | Lightning Impulse Withstand Voltage (Peak Value) | kV | To ground, phase - to - phase: 75; Isolation fracture: 85 |
To ground, phase - to - phase: 75; Isolation fracture: 85 |
| 5 | Rated Short - Circuit Withstand Current | kA | 20 | 20 |
| 6 | Rated Short - Circuit Duration | s | 4 | 4 |
| 7 | Rated Peak Withstand Current | kA | 50 | 50 |
| 8 | Rated Effective Load Breaking Current | A | 630 | 630 |
| 9 | Rated Loop Breaking Current | A | 630 | 630 |
| 10 | Rated Cable Charging Breaking Current | A | 10 | 10 |
| 11 | Rated No - Load Transformer Breaking Capacity | kVA | - | 1600 |
| 12 | Rated Short - Circuit Breaking Current | kA | - | 31.5 |
| 13 | Rated Transfer Current | A | - | 200 |
| 14 | Fuse Model | - | - | SDLAJ - 12, SFLAJ - 12 |
| 15 | Striker Output Energy | J | - | 1 ± 0.5 |
| 16 | Rated Short - Circuit Making Current | kA | 50 | 80 (Expected value) |
| 17 | Earthing Switch Rated Short - Time Withstand Current | kA | - | 20 |
| 18 | Earthing Switch Rated Short - Circuit Duration | s | - | 2 |
| 19 | Earthing Switch Rated Peak Withstand Current | kA | - | 50 |
| 20 | Auxiliary Circuit Rated Voltage | V | ≦ 220 | ≦ 110 |
| 21 | Mechanical Life | Times | 10000 | 10000 |