China GCS Low Voltage Withdrawable Switchgear - High-Quality Power Distribution Solutions from Trusted Suppliers & Factory

The GCS low-voltage withdrawable switchgear is an essential component for power distribution systems across various industries, including power plants, petroleum, chemical engineering, metallurgy, textiles, and skyscrapers. This versatile equipment is particularly advantageous in highly automated environments such as large power plants and petrochemical facilities where computer interfacing is crucial. As a complete low-voltage power distribution solution, it efficiently manages power distribution, centralized motor control, and reactive power compensation in power generation and supply systems. Designed for three-phase AC frequencies of 50(60)Hz and rated working voltages of 380V(400V) or 660V, this switchgear can accommodate a rated current of up to 4000A. Choose our GCS low-voltage withdrawable switchgear from trusted China suppliers and factories to ensure top-quality performance for your power distribution needs

    Overview

    The GCS low-voltage withdrawable switchgear is applicable to the power distribution systems in industries such as power plants, petroleum, chemical engineering, metallurgy, textiles, and high-rise buildings. In places with a high degree of automation such as large-scale power plants and petrochemical systems, where an interface with computers is required, it serves as a low-voltage complete power distribution device for power distribution, centralized control of motors, and reactive power compensation in power generation and supply systems with a three-phase AC frequency of 50(60)Hz, a rated working voltage of 380V(400V), (660V), and a rated current of 4000A and below.

    Performance Indicators

    The design of the device complies with the following standards:

    • IEC 439-1: Low-voltage switchgear and controlgear assemblies
    • GB 7251: Low-voltage switchgear and controlgear assemblies
    • ZBK 36001: Low-voltage withdrawable switchgear assemblies

    Basic Parameters

    Parameter Item Specifications & Value Range
    Rated voltage of auxiliary circuit (V) AC 220, 380(400); DC 110, 220
    Rated frequency (Hz) 50(60)
    Rated insulation voltage (V) 660(1000)
    Rated current (A) - Horizontal busbar ≤4000
    Rated current (A) - Vertical busbar (MCC) 1000
    Rated short-time withstand current of busbar (kA/1s) 50, 80
    Rated peak withstand current of busbar (kA/0.1s) 105, 176
    Power frequency test voltage (V/1min) - Main circuit 2500
    Power frequency test voltage (V/1min) - Auxiliary circuit 1760
    Busbar - Three-phase four-wire system A, B, C, PEN
    Busbar - Three-phase five-wire system A, B, C, PE, N
    Degree of protection IP30, IP40

    Main Structure

    The main framework adopts 8MF-type open-mouth section steel. Two side surfaces of the section steel are respectively provided with mounting holes with module sizes of 20mm, 100mm, and a diameter of Φ9.2mm, enabling flexible and convenient internal installation.

    Assembly Forms

    Designed into two types: a fully assembled structure and a partially (side frames and cross-beams) welded structure, for users to choose from.

    Compartment Isolation

    The functional compartments of the device are isolated from each other. Divided into functional unit, busbar, and cable compartments to keep functions independent.

    Busbar & Cable Design

    Horizontal main busbars adopt a rear-mounted style to resist electric force and withstand short-circuit strength. Cables enter/exit easily from top and bottom.

    The size series of the device's universal cabinet body is detailed in the table below:

    Height (mm) Width (mm) Depth (mm) Options
    2200 400 800, 1000
    600 800, 1000
    800 / 1000 600, 800, 1000
    1000 600, 800, 1000

    Frequently Asked Questions (FAQ)

    What industries are GCS low-voltage withdrawable switchgear suitable for?

    It is widely used in power distribution systems across industries such as power plants, petroleum, chemical engineering, metallurgy, textiles, and high-rise buildings, especially where computer interfaces are needed for automation.

    What are the main functions of GCS switchgear in power systems?

    It serves as a complete low-voltage power distribution device for power distribution, centralized motor control, and reactive power compensation in systems with a three-phase AC frequency of 50(60)Hz.

    Which standards does the GCS switchgear comply with?

    The design complies with international and national standards, including IEC 439-1, GB 7251, and ZBK 36001 for low-voltage switchgear and controlgear assemblies.

    What is the protection rating of the GCS switchgear cabinet?

    The device features an IP30 or IP40 degree of protection, providing reliable safety and dust prevention for internal electrical components.

    How is the main framework of GCS switchgear constructed?

    The main framework is constructed using 8MF-type open-mouth section steel. It features mounting holes with module sizes of 20mm and 100mm, allowing for flexible and convenient internal installation.

    What assembly options are available for the GCS main framework?

    Users can choose between two assembly forms: a fully assembled structure or a partially welded structure (focusing on side frames and cross-beams) depending on project requirements.