China GN19-12 Indoor High Voltage Isolation Switch - Suppliers & Factory for 12KV Power Systems
Overview
GN19-12 series indoor high-voltage isolation relationship high-voltage switchgear is used in power systems with rated voltage of 12KV, AC 50Hz and below. It is equipped with CS6-1 manual operating mechanism and is used for opening and closing circuits under voltage and no load. It also has derivative products such as anti fouling type, high-altitude type, and equipped with live display devices.
The isolation switch in this department is equipped with the CS6-1 manual operating mechanism.
This series of isolating switches is a three pole type, consisting of a chassis, a shaft, a lever, a porcelain pillar insulator, a switch blade, and a terminal block. The rotating shaft is mounted on the chassis and has three pairs of levers welded on it. The levers are connected to a ceramic insulator and a knife chain through a pull rod. The rotating shaft extends out of the chassis, and any section of it can be connected to the operating mechanism.
Type C is a through wall type. Where C1 represents rotation on the through wall side; C2 represents the disconnection on the through wall side; C3 indicates that both sides are on the through wall side.
Model and meaning
Environmental condition of use
- Altitude not exceeding 1000m;
- Surrounding air temperature: -25 ℃~+40 ℃;
- The seismic intensity shall not exceed 8 degrees;
- Relative humidity of the surrounding environment: daily average not exceeding 95%, monthly average not exceeding 90%;
- Installation location: No fire, flammable, explosive, severely polluted, chemically corroded, or violently vibrating areas.
Technical parameter
| Item | Unit | Parameter | ||||||||
| Rated Voltage | KV | 12 | ||||||||
| 1min Power Frequency Withstand Voltage | To ground | KV | 42 | |||||||
| Break | KV | 48 | ||||||||
| Lightning Impulse Withstand Voltage (Peak Value) | To Ground | KV | 75 | |||||||
| Break | KV | 85 | ||||||||
| Rated Frequency | HZ | 50 | ||||||||
| Rated Current | A | 400 | 630 | 1000 1250 | ||||||
| Rated Short - time Withstand Current | KA | 16 | 20 | 16 | 20 | 25 | 20 | 25 | 31.5 | |
| Rated Peak Withstand Current | KA | 40 | 50 | 40 | 50 | 63 | 50 | 63 | 80 | |
| Duration of Rated Short - time Withstand Current Main Switch/Earthing Switch | s | 4/2 | ||||||||
| Creepage Distance | mm | 300 - 380 | ||||||||
| Mechanical Life | Times | 2000 | ||||||||
Appearance and installation size
Product type
| Product type | A | B | C | D | E | F | ||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| GN19-12/400 | 450 | 436 | 4-14x24 | 210 | 230 | 250 | 620 | 660 | 700 | 870 | 900 | 940 |
| GN19-12/630 | 490 | 436 | ||||||||||
|
510 | 530 | 4-18x28 | |||||||||
| GN19-12C/400 | 420 | 625 | 4-14x24 | |||||||||
| GN19-12C/630 | 460 | 625 | ||||||||||
|
505 | 745 | 4-18x28 | |||||||||