China GN30-12(D) Indoor Rotary High Voltage Isolation Switch - Reliable Suppliers & Factory Solutions
Overview
The GN30-12 series indoor rotary high-voltage isolation switch is a new type of isolation switch with a rotating contact blade. The main structural type is on the upper and lower planes of the three-phase common low frame, with two sets of insulators and contacts fixed. By rotating the contact blade, the switch can be opened and closed.
The GN30-12D switch is based on the GN30-12 switch and includes a form with a connecting knife, which can meet the needs of different power systems. This product is designed to be compact, occupy small space, have strong insulation capacity, and are easy to install and adjust. Its performance complies with GB1985-89 "AC High Voltage Isolation.
The requirements of "Leaving Off and Grounding Switches" apply to indoor systems with rated voltage below 10 kV AC 50Hz, used for opening and closing circuits under voltage and no load conditions. It can be used in conjunction with high-voltage switchgear or used independently.
Model and meaning
Condition of use
- Altitude not exceeding 1000m;
- Relative humidity: daily average not exceeding 95%, monthly average not exceeding 90%;
- Places without severe dust, chemical corrosiveness, and explosive substances;
- Earthquake intensity not exceeding 8 degrees;
- Places without frequent and severe vibrations.
Technical parameter
| Model / Parameter | GN30 - 12/400 - 12.5 |
GN30 - 12/630 - 20 |
GN30 - 12/1200 - 31.5 |
GN30 - 12/1250 - 31.5 |
|
GN30 - 12D/400 - 12.5 |
GN30 - 12D/630 - 20 |
GN30 - 12D/1200 - 31.5 |
GN30 - 12D/1250 - 31.5 |
||
Rated Voltage (kV) |
12 |
12 |
12 |
12 |
|
Rated Current (A) |
400 |
630 |
1200 |
1250 |
|
Thermal Stable Current (kA) |
12.5 |
20 |
31.5 |
31.5 |
|
Thermal Stable Time (s) |
4 |
4 |
4 |
4 |
|
Dynamic Stable Current (kA) |
31.5 |
50 |
80 |
80 |
|
Rated Insulation Level |
Lightning Impulse Voltage (kV) |
Phase - to - phase, Phase - to - ground 75, Break 85 |
Phase - to - phase, Phase - to - ground 75, Break 85 |
Phase - to - phase, Phase - to - ground 75, Break 85 |
Phase - to - phase, Phase - to - ground 75, Break 85 |
1min Power Frequency Voltage (kV) |
|||||
Appearance and installation size