China KYN28-12 (GZSArmoured AC Metal Enclosed Switchgear Suppliers & Factory for 3-12kV Power Distribution

The KYN28-12 (GZSindoor metal armored mid-mounted withdrawable switchgear is an advanced solution for three-phase AC 50Hz indoor distribution. Designed specifically for the effective reception and distribution of 3-12kV network power, this switchgear plays a critical role in controlling, protecting, and monitoring electrical circuits. As a leading product from China, this switchgear embodies the high standards of quality and reliability that you expect from trusted suppliers and factories in the electrical equipment industry. Choose our KYN28-12 switchgear for superior performance and safety in your power distribution needs

    Overview

    This product's relay chamber panel can be equipped with various types of microcomputer based comprehensive relay protection devices, and can achieve intelligent control of the system. It has remote control, telemetry, remote signaling, and remote adjustment functions, and controls the field network through a CAN bus with a communication interface. This cabinet can be equipped with VSI (i.e. ZN63), ZN12V vacuum circuit breakers, as well as imported VD4 vacuum circuit breakers and VC series vacuum contactors.

    The "Five Prevention" Safety Functions:
    • Preventing misoperation of circuit breakers.
    • Preventing pushing handle carts with loads.
    • Preventing live closing of grounding switches.
    • Preventing grounding switches from transmitting power in the grounding position.
    • Preventing accidental entry into live intervals.
    Environmental Conditions for Use
    Temperature & Altitude

    Surrounding air temperature: Upper limit +40 ℃, lower limit -10 ℃ in general areas.

    Altitude: Standard up to 1000m.

    Humidity & Water Vapor

    Relative humidity: Daily average ≤ 95%, monthly average ≤ 90%.

    Water vapor pressure: Daily average ≤ 2.2KPa, monthly average ≤ 1.8KPa.

    When the temperature drops sharply, condensation may occur, accompanied by contamination. This product is suitable for the following two environmental conditions that are more severe than normal:

    • (1). Not frequent condensation (no more than twice a month on average) with mild pollution;
    • (2). Generally, there is no condensation (no more than twice a year on average) and there is relatively serious pollution;

    Harsh Environments: There is no danger of fire, explosion, or severe pollution that can corrode metals and damage insulation. Fits places without severe vibrations, bumps, and vertical inclinations not exceeding 80 degrees.

    Notes:
    • Storage and transportation are allowed at -30 ° C.
    • When the altitude exceeds 1000m, it shall be handled in accordance with JB/2102 "Technical Requirements for High Voltage Electrical Appliances in High Altitude Areas". When the altitude does not exceed 2000m, no measures need to be taken for low-voltage auxiliary equipment.
    • When the actual usage conditions differ from the above, both the user and the manufacturer should negotiate.
    Schematic Diagram of Switchgear Structure
    Schematic diagram of switchgear structure
    Structure Compartments & Components
    A - Circuit breaker compartment
    B - Busbar compartment
    C - Cable room
    D - Relay instrument room
    1 - Busbar
    2 - Static contact box
    3 - Circuit breaker
    4 - Grounding switch
    5 - Current Transformer
    6 - Capacitive voltage divider
    7 - Lightning arrester
    Detailed schematic diagram of switchgear structure
    Detailed Component Breakdown
    1.1 - Pressure relief device
    1 - Shell
    2 - Branch small busbar
    3 - Busbar bushing
    4 - Main busbar
    5 - Static contact device
    6 - Static contact box
    7 - Current Transformer
    8 - Grounding switch
    9 - Cable
    10 - Lightning arrester
    11 - Grounding main busbar
    12 - Loading/unloading partition
    13 - Partition (valve)
    14 - Secondary plug
    15 - Circuit breaker handcart
    16 - Heater device
    17 - Removable horizontal partition
    18 - Grounding switch mechanism
    1.2 - Control small cable trays
    19 - Bottom plate
    Compliant with Standards

    This product is designed and manufactured to meet rigorous industry standards, ensuring safety, reliability, and global compatibility:

    IEC-298 GB3906-1991 DL/T404-1997 GB/T11022-1999
    Frequently Asked Questions (FAQ)
    What are the "five prevention" features of this switchgear?

    The "five prevention" features include preventing misoperation of circuit breakers, preventing pushing handle carts with loads, preventing live closing of grounding switches, preventing grounding switches from transmitting power in the grounding position, and preventing accidental entry into live intervals.

    Which types of vacuum circuit breakers can be installed?

    This cabinet can be equipped with VSI (i.e. ZN63) and ZN12V vacuum circuit breakers, as well as imported VD4 vacuum circuit breakers and VC series vacuum contactors.

    What are the temperature limits for standard operations?

    The surrounding air temperature limits are an upper limit of +40 ℃ and a lower limit of -10 ℃ in general areas. Storage and transportation are allowed down to -30 ° C.

    What is the altitude limit and how is higher altitude handled?

    The standard altitude limit is 1000m. If the altitude exceeds 1000m, it must be handled in accordance with the JB/2102 standard. However, if the altitude does not exceed 2000m, no additional measures are required for low-voltage auxiliary equipment.

    What communication and control functions are supported?

    The system supports remote control, telemetry, remote signaling, and remote adjustment functions, and controls the field network through a CAN bus communication interface.