China KYN61-40.5 Metalclad & Withdrawable AC Switchgear Suppliers & Factory for 40.5kV Power Systems
Overview
The KYN61-40.5 Metalclad & Withdrawable AC Switchgear (hereinafter referred to as switchgear) is a three - phase AC 50Hz, rated voltage 40.5kV indoor complete power distribution device. It is used in power plants, substations, and industrial and mining enterprises for receiving and distributing electrical energy, and plays a role in controlling, protecting, and detecting circuits. It can also be used in places with frequent operations. This switchgear complies with standards such as GB/T11022 - 1999, GB3906 - 2006, and DL404 - 1997.
Structural Features
- The cabinet structure adopts an assembled type, and the circuit breaker adopts a handcart floor - type structure.
- It is equipped with a new - type composite insulation vacuum circuit breaker, which has the characteristics of good interchangeability and simple replacement.
- The handcart frame is equipped with a lead - screw nut advancing mechanism, which can easily move the handcart and prevent damage to the advancing structure due to misoperation.
- All operations can be carried out with the cabinet door closed.
- The interlocks among the main switch, handcart, and switchgear door all adopt a mandatory mechanical interlocking method to meet the "five - prevention" functions.
- The cable room has sufficient space and can connect multiple cables.
- The quick - earthing switch is used for earthing and loop short - circuit.
- The protection level of the enclosure is IP3X, and when the handcart room door is open, the protection level is IP2X.
- The product complies with GB3906 - 1991, DL404 - 1997, and refers to the international IEC - 298 standard.3.Schematic.
Model Meaning
Service Environment Conditions
- Upper limit of ambient temperature: +40°C, and the average value measured within 24 hours shall not exceed 35°C; lower limit: -15°C.
- Altitude: Not exceeding 1000 meters.
- Relative humidity: Daily average value not exceeding 95%, monthly average value not exceeding 90%.
- Earthquake intensity: Not exceeding magnitude 8.
- Water vapor pressure: Daily average value not exceeding 2.2kPa, monthly average value not exceeding 90%.
Technical Parameters
Frequently Asked Questions (FAQ)
What is the rated voltage and application of the KYN61-40.5 switchgear?
The KYN61-40.5 switchgear is a three-phase AC 50Hz indoor complete power distribution device with a rated voltage of 40.5kV. It is primarily used in power plants, substations, and industrial enterprises to receive and distribute electrical energy while controlling, protecting, and detecting circuits.
Can the switchgear be operated with the doors closed?
Yes, all operations of the KYN61-40.5 switchgear can be safely carried out while the cabinet door is completely closed, ensuring enhanced safety for operating personnel.
What are the ambient temperature limits for this equipment?
The switchgear is designed to operate within an ambient temperature range of -15°C (lower limit) to +40°C (upper limit). Additionally, the average temperature measured over a 24-hour period should not exceed 35°C.
What is the protection level of the KYN61-40.5 enclosure?
The enclosure features a standard protection level of IP3X. When the handcart room door is open, the protection level is rated at IP2X.
What safety interlocks are integrated into the switchgear?
The interlocks among the main switch, handcart, and switchgear door utilize a mandatory mechanical interlocking method. This robust mechanical system is designed to meet the strict "five-prevention" safety requirements.
Which standards does the switchgear comply with?
The product complies with Chinese national and industry standards including GB/T11022-1999, GB3906-2006, and DL404-1997. Its design also references the international standard IEC-298.