China LSY-10/110 Current Transformer Suppliers - Medium Voltage Power System Factory Solution for Accurate Measurement
Overview
The LSY-10 current transformer is a three-phase integrated combined current transformer, specifically designed for measurement and protection tasks in medium-voltage power systems.
It is suitable for AC power systems of 10kV and below, capable of accurately measuring three-phase current and zero-sequence current, and is widely used in current monitoring scenarios such as ring main unit switchgear, pole-mounted switches, and multiple cable circuits.
This transformer is uniquely designed. Its core and secondary winding are vacuum-cast with high-quality epoxy resin and sealed in a flame-retardant plastic housing. This design not only effectively prevents the equipment from being eroded by a humid environment but also ensures the long-term stability of product performance with almost no maintenance required, greatly reducing operating costs. In practical applications, the LSY-10 can convert the large current on the primary side into a small current on the secondary side in proportion, facilitating the access of measuring instruments and protection devices, and providing reliable data support for the safe and stable operation of the power system.
Product Advantages
The LSY-10 current transformer has many significant advantages, making it an ideal choice for current measurement and protection in medium-voltage power systems:
High Precision
Its high-precision measurement performance can provide accurate data for the metering and monitoring of the power system, helping to improve the operating efficiency of the power system.
High Reliability
Stems from its excellent materials and exquisite craftsmanship, enabling it to work stably in harsh environments and reducing the probability of failures.
Easy Installation
Its compact structural design makes installation in various switchgear and cable lines simple and efficient, saving valuable time and labor costs.
In summary, the LSY-10 current transformer, with its excellent performance, reliable quality, and convenient installation method, has become an ideal choice for current measurement and protection in medium-voltage power systems, escorting the stable operation of modern power networks.
Technical Parameters of LSY-10 Current Transformer
| Item | Parameter |
|---|---|
| Rated Frequency | 50Hz or 60Hz |
| Rated Secondary Current | 5A or 1A |
| Rated Short-time Thermal Current | 40kA, 1s |
| Rated Continuous Thermal Current | 120%In |
| Load Power Factor | COSφ = 0.8 (lagging) |
| Instrument Security Factor | FS≤10 |
| Accuracy Limitation Factor (Protection) | 10P10, 10P15, 10P20, etc. |
| Ambient Temperature | -25ºC to +40ºC |
| Average Daily Temperature | ≤40ºC |
| Altitude | ≤3000m |
| Pollution Class | III |
| Power-frequency Withstand Voltage | 3kV, 1min |