China MCB Suppliers - High-Quality Miniature Circuit Breaker from Trusted Factory for Overload and Short Circuit Protection
Overview
MCB (Miniature Circuit Breaker) is a commonly used protective device for building electrical terminal distribution. It is used for single-phase and three-phase circuits below 125A. It can protect against short circuit, overload, overvoltage and other faults. There are single-pole 1P, two-pole 2P, three-pole 3P, four-pole 4P and other types.
It consists of operating mechanism, contacts, release (overcurrent, thermal, undervoltage, etc.), and arc extinguishing system. In normal conditions, the circuit is manually switched on and off. In overload, the bimetallic strip of the thermal release is bent due to heat. In short circuit, the armature of the overcurrent release is attracted, which will push the free tripping mechanism to disconnect the main circuit. In undervoltage, the armature of the undervoltage release is released, which will also trigger the disconnection.
According to the instantaneous tripping current, it is divided into B, C, and D types: Type B trips at 3-5 times the rated current, suitable for resistive/small inductive loads such as residential buildings; Type C trips at 5-10 times, suitable for commercial and industrial scenarios with high inductive loads such as small motors and fluorescent lamps; Type D trips at 10-25 times, used in special occasions with high inductive and high surge currents such as X-ray machines and large winding motors, and can achieve protection within one tenth of a second. It can also be divided into single-pole, double-pole, etc. according to the number of poles. The selection needs to match the line voltage, calculated current, short-circuit current, etc. to ensure reliable protection and avoid false tripping or refusal to trip, providing basic protection for the safe operation of circuits and equipment in home, commercial, and industrial power distribution systems.
Product Features
Precise Protection
Integrates overload and short - circuit protection; some models add over - voltage and leakage protection. Tripping curves (Type B/C/D, etc.) match different loads (resistive, inductive), rapidly interrupting faulty circuits.
Compact Design
Encapsulated in a molded flame - retardant housing, featuring a space - saving structure. Ideal for installation in distribution boxes and electrical control cabinets with limited space.
Easy Operation
Manual switching with clear status indication. DIN - rail mountable for simplified wiring, maintenance, and replacement.
Safe & Reliable
Flame - retardant and insulated housing, paired with mature arc - quenching design. Effectively suppresses arc hazards, ensuring electrical safety.
Wide Current Range
Rated currents typically 6A–125A, covering small - current branch protection for residential, commercial, and industrial end - use distribution.
Versatile Application
Available in 1P to 4P configurations, compatible with single - phase/three - phase circuits. Suits lighting, socket, and small - motor circuits.
Product Parameters
| Parameter Category | Technical Specifications | Explanation/Standard Reference |
|---|---|---|
| Rated Voltage (Ue) | AC 230V/400V (common); DC 250V (DC type) | Compatible with low-voltage distribution systems (IEC 60898-1) |
| Rated Current (In) | 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A | Covers end-branch protection requirements (GB 10963.1) |
| Breaking Capacity (Icu/Ics) | Standard: 6kA/4.5kA; High breaking: 10kA/7.5kA; Ultra-high breaking: 15kA/11.25kA (400V) | Indicates short-circuit interruption capability (IEC 60898-1 4.5.3) |
| Tripping Curve Type | Types B, C, D (some with K, Z types) | - Type B (3–5In): Resistive loads (lighting) |
| - Type C (5–10In): General inductive loads (sockets) | ||
| - Type D (10–20In): High-inductive loads (small motors) (IEC 60898-1 4.3.3) | ||
| Pole Configuration | 1P, 1P+N, 2P, 3P, 4P | Suits single-phase/three-phase systems (GB 10963.1 5.1) |
| Protection Functions | Basic: Overload (inverse-time), short circuit (instantaneous) | Overload protection complies with IEC 60898-1 4.3.2 inverse-time characteristics |
| Extended: Leakage (with RCCB), overvoltage/undervoltage | ||
| Mechanical Life | ≥20,000 operations (make/break cycles) | Impacts long-term reliability (IEC 60898-1 8.10) |
| Electrical Life | ≥4,000 operations (at rated current) | Related to contact durability (IEC 60898-1 8.11) |
| Protection Class | IP20 (housing); IP40 with protective cover (optional) | Dust and foreign object protection (IEC 60529) |
| Wiring Method | Front connection, rear connection, plug-in type | Adapts to different installation scenarios (GB 10963.1 6.2) |