Key Advantages
Excellent insulation and arc extinguishing performance:
The RM6 device makes full use of the excellent insulation and arc extinguishing performance of SF6 gas to effectively prevent electrical faults, thereby ensuring the stable operation of the power system.
Versatile modular design:
The device is designed with modularity as the core, and electrical components such as circuit breakers, load switches and earthing switches can be customized according to specific needs to provide customized power distribution solutions.
Space-saving structure:
Its design focuses on compactness, which can be easily installed and used even in space-constrained environments, thereby optimizing the installation space.
Easy operation and maintenance:
The device adopts a front operation design and does not require internal maintenance, which significantly improves the safety and convenience of operation. The simplified maintenance process helps to reduce operating and maintenance costs.
Environmental management:
The device adopts an SF6 gas closed-loop system and an environmentally friendly design approach to minimize the impact on the environment. It is also carefully designed for easy recycling and disposal, which meets environmental requirements.
Comprehensive protection:
The RM6 device provides a range of protection functions, including overload and short-circuit protection, to ensure that the power grid and connected equipment remain safe and stable under various conditions.
Product Parameters
| Item | Unit | C Module (Load Switch) |
F Module (Combined Apparatus) |
V Module (Vacuum Switch) |
Isolation/ Earthing Switch |
CB Module (Vacuum Circuit Breaker) |
Isolation/ Earthing Switch |
|---|---|---|---|---|---|---|---|
| Rated Voltage | KV | 12 | 12 | 12 | 12 | 12 | 12 |
| Rated Frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 |
| Power Frequency Withstand Voltage (PhasetoPhase / Port) | kV | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 |
| Lightning Impulse Withstand Voltage | kV | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 |
| Rated Current | A | 630 | Note ¹ | 630 | - | 1250/630 | 1450 |
| Breaking Capability | - | - | - | - | - | - | - |
| Rated Loop Breaking Current | A | 630 | - | - | - | - | - |
| Rated Cable Charging Breaking Current | A | 10 | - | - | - | - | - |
| Rated ShortCircuit Making Current (Peak) | A | 50 | - | - | - | - | - |
| Rated Peak Withstand Current | kA | 50 | 80 | - | - | - | - |
| Rated ShortTime Withstand Current | kA/35 | 20 | - | 20 | - | - | - |
| Rated ShortCircuit Breaking Current | kA | - | 31.5 | 20 | - | 25 | - |
| Rated Transfer Current | A | - | 1700 | - | - | - | - |
| Maximum Current of Equipped Fuse | A | - | 125 | - | - | - | - |
| Loop Resistance | μΩ | ≤ 300 | ≤ 600 | - | - | - | - |
| Mechanical Life | Times | 5000 | 3000 | 5000 | 2000 | 5000 | 5000 |
| Note ¹: Depends on the current rating of the fuse | |||||||
Frequently Asked Questions
What are the primary insulation benefits of the RM6 device?
The RM6 device utilizes SF6 gas, which provides outstanding insulation and arc extinguishing performance. This helps prevent electrical faults effectively and ensures the continuous, stable operation of the power grid.
Can the RM6 configuration be customized for different applications?
Yes, the RM6 features a highly versatile modular design. Depending on your specific power distribution needs, electrical components such as vacuum circuit breakers, load switches, and earthing switches can be customized and combined.
Is the RM6 suitable for installations with limited space?
Absolutely. The compact design of the RM6 is specifically engineered to optimize space, making it easy to install and operate even in highly space-constrained environments.
What makes the RM6 easy to operate and maintain?
The RM6 is designed with a user-friendly front-operation interface and does not require internal maintenance. This design minimizes operational complexity, enhances user safety, and significantly lowers long-term maintenance costs.
How does the RM6 address environmental concerns?
The device features an SF6 gas closed-loop system that prevents gas leakage and minimizes environmental impact. Furthermore, the materials and components are designed for easy recycling and disposal at the end of their lifecycle.
What protection capabilities does the RM6 offer?
The RM6 provides comprehensive protection features, including overload and short-circuit protection, to safeguard both the connected electrical equipment and the wider power distribution network under all operating conditions.