China SF6 HV Load Switch FLRN36-12D - Reliable High Voltage Switchgear Suppliers & Factory
Overview
The FLRN36 - 12D SF₆ high - voltage load switch is an indoor switchgear applicable to three - phase AC 10kV, 50Hz power systems. It uses SF₆ gas as the arc - extinguishing and insulating medium, integrating three functions of closing, opening, and grounding into one unit, and is sealed in an epoxy resin shell filled with SF₆ gas, featuring a compact structure. It has characteristics such as reliable interlocking, high insulation strength of fracture ports, and maintenance - free operation. It can be matched with complete sets of power distribution equipment, ring - main switch cabinets, etc., and is used in scenarios like urban network renovation and industrial and mining enterprises to realize power distribution, control, and protection. Moreover, it can be adapted to intelligent units to achieve “three remotes” (remote control, remote signaling, remote measurement). It has a fast fault - breaking speed, which is beneficial for system stability.
Product Features
Efficient Arc - Extinguishing & Insulation
Leverages SF₆ gas for strong arc - quenching and stable insulation, ensuring high - strength fracture port insulation per GB 3906.
Integrated Functionality
Combines closing, opening, and grounding in one compact epoxy - resin - sealed unit, simplifying cabinet layout.
Reliable Interlocking
Mechanical/electrical interlocks prevent misoperations, aligning with DL/T 534 for safe grid operation.
Maintenance - Free Design
Sealed SF₆ system avoids regular refilling, reducing lifecycle costs.
Smart Compatibility
Pairs with intelligent units for “three remotes” (control, signaling, measurement), enabling digital grid integration.
Fast Fault Handling
Rapid fault interruption stabilizes systems, ideal for urban networks/industrial applications per GB/T 11022.
Product Parameters
| No. | Item | Unit | Data |
|---|---|---|---|
| 1 | Rated voltage | KV | 12 |
| 2 | Rated frequency | Hz | 50 |
| 3 | Rated current | A | 630 |
| 4 | Rated peak withstand current | KA | 50 |
| 5 | 4s rated short time withstand current | KA | 20 |
| 6 | Rated making current | KA | 50 |
| 7 | Rated breaking current - Active load breaking current | A | 630 |
| Rated breaking current - Breaking current loop | A | 630 | |
| Rated breaking current - Cable charging breaking current | A | 10 | |
| 8 | 1min power frequency withstand voltage (phase to phase, to earth, fracture) | KV | 42/48 |
| 9 | Lightning impulse withstand voltage (phase to phase, to earth, fracture) | KV | 75/85 |
| 10 | Relative pressure of SF6 gas (20℃ GP) | MPa | ≤0.04 |
| 11 | Rated operating voltage (electric) | V | AC220、DC220 |
| 12 | Rated voltage of shunt release | V | AC220、DC220 |
| 13 | Average opening speed | m/s | 3.5±1.5 |
| 14 | Average closing speed | m/s | 3.5±1.5 |
| 15 | Three - phase points, closing phase of the same | ms | ≤3 |
| 16 | The main circuit resistance | μΩ | ≤120 |
| 17 | Manual maximum torque | N.m | ≤160 |
| 18 | phase to phase center distance | mm | 210±0.5 |
Frequently Asked Questions (FAQ)
Q: What is the primary application of the FLRN36-12D load switch?
A: The FLRN36-12D is an indoor switchgear designed for three-phase AC 10kV, 50Hz power systems. It is widely used in urban network renovation, industrial and mining enterprises, and ring-main switch cabinets to achieve power distribution, control, and system protection.
Q: How does the switch ensure reliable arc-extinguishing and insulation?
A: It utilizes SF₆ (sulfur hexafluoride) gas as the arc-extinguishing and insulating medium. The internal components are sealed within a high-durability epoxy resin shell, which provides high insulation strength at the fracture ports complying with GB 3906 standards.
Q: What functions are integrated into this single unit?
A: The FLRN36-12D integrates three essential operations into one compact unit: closing, opening, and grounding. This multi-functional integration simplifies overall switchgear cabinet layout and saves installation space.
Q: Does the FLRN36-12D support smart grid operations?
A: Yes, it can be adapted to intelligent control units to achieve "three remotes" capabilities, which include remote control, remote signaling, and remote measurement for modernized grid management.
Q: Is regular maintenance required for the gas system?
A: No, the switch features a maintenance-free design. The SF₆ gas system is permanently sealed inside the epoxy resin shell, preventing gas leakage and eliminating the need for regular gas refilling during its service life.
Q: What safety interlocking mechanisms are built into the switch?
A: It incorporates reliable mechanical and electrical interlocks designed to prevent operational errors, ensuring high grid safety and alignment with DL/T 534 specifications.