China SF6 HV Load Switch FLRN36-12D - Reliable High Voltage Switchgear Suppliers & Factory

The FLRN36 - 12D SF₆ high-voltage load switch is an innovative indoor switchgear designed for three-phase AC power systems operating at 10kV and 50Hz. Manufactured in China, this state-of-the-art device leverages SF₆ gas as both the insulating and arc-extinguishing medium, ensuring optimal performance. The switch seamlessly integrates the crucial functions of closing, opening, and grounding into a compact unit, all housed within a durable epoxy resin shell filled with SF₆ gas. As a leading supplier in the industry, our factory produces load switches known for their reliable interlocking features, exceptional insulation strength at fracture ports, and a maintenance-free operation that meets the highest standards. Equip your power systems with this advanced technology and experience superior reliability and efficiency

    Overview

    The FLRN36 - 12D SF₆ high - voltage load switch is an indoor switchgear applicable to three - phase AC 10kV, 50Hz power systems. It uses SF₆ gas as the arc - extinguishing and insulating medium, integrating three functions of closing, opening, and grounding into one unit, and is sealed in an epoxy resin shell filled with SF₆ gas, featuring a compact structure. It has characteristics such as reliable interlocking, high insulation strength of fracture ports, and maintenance - free operation. It can be matched with complete sets of power distribution equipment, ring - main switch cabinets, etc., and is used in scenarios like urban network renovation and industrial and mining enterprises to realize power distribution, control, and protection. Moreover, it can be adapted to intelligent units to achieve “three remotes” (remote control, remote signaling, remote measurement). It has a fast fault - breaking speed, which is beneficial for system stability.

    Product Features

    Efficient Arc - Extinguishing & Insulation

    Leverages SF₆ gas for strong arc - quenching and stable insulation, ensuring high - strength fracture port insulation per GB 3906.

    Integrated Functionality

    Combines closing, opening, and grounding in one compact epoxy - resin - sealed unit, simplifying cabinet layout.

    Reliable Interlocking

    Mechanical/electrical interlocks prevent misoperations, aligning with DL/T 534 for safe grid operation.

    Maintenance - Free Design

    Sealed SF₆ system avoids regular refilling, reducing lifecycle costs.

    Smart Compatibility

    Pairs with intelligent units for “three remotes” (control, signaling, measurement), enabling digital grid integration.

    Fast Fault Handling

    Rapid fault interruption stabilizes systems, ideal for urban networks/industrial applications per GB/T 11022.

    Product Parameters

    No. Item Unit Data
    1 Rated voltage KV 12
    2 Rated frequency Hz 50
    3 Rated current A 630
    4 Rated peak withstand current KA 50
    5 4s rated short time withstand current KA 20
    6 Rated making current KA 50
    7 Rated breaking current - Active load breaking current A 630
    Rated breaking current - Breaking current loop A 630
    Rated breaking current - Cable charging breaking current A 10
    8 1min power frequency withstand voltage (phase to phase, to earth, fracture) KV 42/48
    9 Lightning impulse withstand voltage (phase to phase, to earth, fracture) KV 75/85
    10 Relative pressure of SF6 gas (20℃ GP) MPa ≤0.04
    11 Rated operating voltage (electric) V AC220、DC220
    12 Rated voltage of shunt release V AC220、DC220
    13 Average opening speed m/s 3.5±1.5
    14 Average closing speed m/s 3.5±1.5
    15 Three - phase points, closing phase of the same ms ≤3
    16 The main circuit resistance μΩ ≤120
    17 Manual maximum torque N.m ≤160
    18 phase to phase center distance mm 210±0.5

    Frequently Asked Questions (FAQ)

    Q: What is the primary application of the FLRN36-12D load switch?

    A: The FLRN36-12D is an indoor switchgear designed for three-phase AC 10kV, 50Hz power systems. It is widely used in urban network renovation, industrial and mining enterprises, and ring-main switch cabinets to achieve power distribution, control, and system protection.

    Q: How does the switch ensure reliable arc-extinguishing and insulation?

    A: It utilizes SF₆ (sulfur hexafluoride) gas as the arc-extinguishing and insulating medium. The internal components are sealed within a high-durability epoxy resin shell, which provides high insulation strength at the fracture ports complying with GB 3906 standards.

    Q: What functions are integrated into this single unit?

    A: The FLRN36-12D integrates three essential operations into one compact unit: closing, opening, and grounding. This multi-functional integration simplifies overall switchgear cabinet layout and saves installation space.

    Q: Does the FLRN36-12D support smart grid operations?

    A: Yes, it can be adapted to intelligent control units to achieve "three remotes" capabilities, which include remote control, remote signaling, and remote measurement for modernized grid management.

    Q: Is regular maintenance required for the gas system?

    A: No, the switch features a maintenance-free design. The SF₆ gas system is permanently sealed inside the epoxy resin shell, preventing gas leakage and eliminating the need for regular gas refilling during its service life.

    Q: What safety interlocking mechanisms are built into the switch?

    A: It incorporates reliable mechanical and electrical interlocks designed to prevent operational errors, ensuring high grid safety and alignment with DL/T 534 specifications.

    Leave Your Message