China Suppliers DFW Premium European-Style High Voltage Cable Branch Box Series for 10kV, 24kV, and 35kV Systems
Scope of Application
The DFW high-voltage cable branch box series is widely used for node connections in 35kV, 24kV, and 10kV cable systems. It is the main electrical equipment for collecting and tapping cables after they exit the switchgear.
The cable joints of the distribution box are insulated with high-grade imported rubber tightly wrapped insulation, without exposed live parts; Switches with switch distribution boxes are all SF6 insulated load switches.
The DFW branch box is designed for outdoor maintenance free operation, ensuring safety and reliability. Its protection level reaches IP33, and the underground tap can withstand flooding. This product is widely used in urban industrial communities, residential areas, commercial centers, mining areas, large enterprises such as steel, automobiles, petroleum, chemical, cement, and other occasions for power distribution networks. It is particularly suitable for urban power grid renovation projects, which can greatly save electrical equipment and cable investment and improve power supply reliability.
Features
Compact structure, small footprint, easy installation, convenient operation, and maintenance free.
The box body is entirely made of metal steel plates or stainless steel plates, with a thickness of 2mm. It adopts anti-corrosion design and special painting treatment, and can operate reliably in harsh environments (with a service life of ≥ 30 years).
Outdoor all-weather, fully protected structure, suitable for high temperature, severe cold, flood immersion, and high dust areas.
Fully sealed and insulated structure, no insulation distance required. The high-voltage live parts are all prefabricated cable connectors made of silicone rubber or EPDM, effectively ensuring personal safety.
Flexible combinations can enable up to seven branch lines, which can be combined with SF6 load switches to form a ring network power supply, fully meeting various wiring requirements.
The cable joint can be used as a switch, with load plug and unplug, to disconnect 200A load current.
After installing the fault indicator, it can quickly detect circuit faults.
Small one-time investment, reducing cable length, not occupying building area, saving funds.
Technical Parameters
| Parameter Item | Technical Specification |
|---|---|
| Rated voltage | 12kV |
| Rated current | 630A |
| Dynamic stable current | 50kA/0.3s |
| Thermal stability current | 20kA/3s |
| 1-minute power frequency withstand voltage | 42kV |
| 15 minute DC withstand voltage | 52kV |
| Lightning impulse withstand voltage | 105kV |
| Box protection level | IP33 |
Model and Meaning