China Suppliers Factory FKRN12-12D Indoor High-Voltage Puffer-Type Load Break Switch/Fuse Combination Apparatus
Overview
Production Features
Compact Structure, Small Footprint
Modular design allows easy integration into switchgear panels, saving installation space.
Puffer-Type Arc Extinguishing Technology
Utilizes compressed air arc extinguishing for strong breaking capacity and effective arc suppression.
Integrated Multi-Functionality
Combines load break switch and fuse, providing disconnection, load breaking, and protection in one unit.
Fast Fault Interruption
High-speed fuse clearing ensures quick isolation of fault currents, minimizing equipment damage.
Visible Isolation Gap
Provides a clearly visible disconnection point to ensure maintenance safety and meet interlocking requirements.
Flexible Operation Options
Supports both manual and motorized operation, suitable for local or remote control.
Long Mechanical Life, Low Maintenance
Designed for over 2000 operations with a robust mechanism and reduced service requirements.
Wide Application Adaptability
Suitable for urban and rural power networks, compact substations, and ring main units (RMUs).
Standards Compliance & High Reliability
Compliant with GB3804, GB16926 and other relevant standards, ensuring high interchangeability and reliability.
Product Parameter
| No. | Item | Unit | FKN12-12D | FKRN12-12D |
|---|---|---|---|---|
| 1 | Rated Voltage | kV | 12 | 12 |
| 2 | Rated Frequency | Hz | 50 | 50 |
| 3 | Rated Current | A | 630 | 125 |
| 4 | Lightning Impulse Withstand Voltage | kV | Phase to earth 42, across isolating gap 48 | Phase to earth 42, across isolating gap 48 |
| 5 | 1min Power Frequency Withstand Voltage | kV | Phase to earth 75, across isolating gap 85 | Phase to earth 75, across isolating gap 85 |
| 6 | Rated Short-Time Withstand Current | kA | Load break switch: 20; Earthing switch: 20 | - |
| 7 | Rated Short-Time Withstand Duration | s | Load break switch: 4; Earthing switch: 2 | - |
| 8 | Rated Peak Withstand Current (Peak) | kA | 50 | - |
| 9 | Rated Breaking Current | A | Load break switch: 630; Close-open breaking current: 630; 5% Rated load breaking current: 31.5; Cable charging current: 10 |
|
| 10 | Rated Transformer Breaking Capacity | kVA | 1250 | - |
| 11 | Rated Short-Circuit Breaking Current (Fuse-linked) | kA | - | 31.5 |
| 12 | Rated Transfer Current | A | 1200 | - |
| 13 | Mechanical Life | times | 2000 | - |
| 14 | Operating Sequence | - | 0-0.3s-CO-180s-CO | - |
| 15 | Closing Time | ms | ≤65 | - |
| 16 | Opening Time | ms | ≤10 | - |
Frequently Asked Questions
What are the primary applications for the FKN12-12 series?
They are designed for 12kV and below three-phase systems, widely used in urban/rural power grids, terminal substations, box-type substations, and ring main units (RMUs) for transformer and cable protection.
What is the difference between FKN12-12D and FKRN12-12D?
The FKN12-12D functions primarily as a load break switch, whereas the FKRN12-12D is a switch-fuse combination apparatus that integrates high-speed fuse protection to interrupt short-circuit faults up to 31.5kA.
How does the puffer-type arc extinguishing technology work?
It utilizes compressed air generated during the switch operation to extinguish the electrical arc rapidly, ensuring reliable and safe current interruption.
Does the FKN12-12 support remote operations?
Yes, it features flexible operation options, supporting both manual control mechanisms and motorized mechanisms for remote system integration.
What safety mechanisms are built into the switch?
It includes a clearly visible isolation gap to guarantee maintenance safety, and it complies with GB3804 and GB16926 standards for interlocking requirements.