The FZN25-12 T type indoor high-voltage AC vacuum load switches and the FZRN25-12D type indoor high-voltage AC vacuum load switch-fuse combination appliances are essential control and protection devices designed for three-phase AC 50Hz, 12kV power distribution systems. Manufactured in China, these products are oil-free, non-toxic, and pose no fire or explosion hazards, making them safe for widespread use in industrial and mining enterprises, urban building substations, and other environments. Compared to traditional circuit breakers, our vacuum load switches provide more reliable protection for electrical equipment, such as transformers. They are particularly well-suited for applications in ring network systems, dual-radial power supply units, and compact substations. As a leading supplier and factory of high-voltage equipment in China, we are committed to delivering quality solutions for your power distribution needs

    Overview

    The FZN25 - 12 T type indoor high - voltage AC vacuum load switches and the FZRN25 - 12D type indoor high - voltage AC vacuum load switch - fuse combination appliances are control and protection devices for three - phase AC 50Hz, 12kV power distribution systems. The products are oil - free, non - toxic, and free from fire and explosion hazards, and are widely used in industrial and mining enterprises, urban building substations and other places. The latter has more reliable protection for electrical equipment such as transformers than circuit breakers, and is especially suitable for ring network, dual - radial power supply units and compact substations.

    The FZN25 - 12 type indoor high - voltage AC vacuum load switch (hereinafter referred to as the load switch) is an indoor device with three - phase AC 50Hz and rated voltage 12kV, suitable for industrial and mining enterprise distribution substations and power stations and other places. It serves as protection and control for electrical facilities, and is used for breaking load current, loop current, no - load transformers and cable charging current. It has the ability to close short - circuit current. Its opening and closing operation mechanism can be manual and electric, facilitating the realization of three - remote control requirements for the power system.

    The FZN25 - 12 type indoor high - voltage AC vacuum load switch - fuse combination appliance (hereinafter referred to as the combination appliance) is an indoor device with three - phase AC 50Hz and rated voltage 12kV, suitable for industrial and mining enterprise distribution substations and power stations and other places. It is used for load control and short - circuit protection. It also has an earthing switch with the ability to close short - circuit current. Its operating mechanism can be manual and electric, facilitating the realization of three - remote control requirements for the power system.

    Main Technical Parameters

    No. Item Unit FZN25 - 12/T630/20 FZRN25 - 12D/T200/31.5
    - Product Type - FZN25 - 12/T630/20 FZRN25 - 12D/T200/31.5
    1 Rated Voltage kV 12 12
    2 Rated Current A 630 200
    3 Rated Frequency Hz 50 50
    4 Rated Insulation Level
    - 1min Power - Frequency Withstand Voltage kV Interrupter fracture: 30; To ground, phase - to - phase: 42; Isolation fracture: 48 Interrupter fracture: 30; To ground, phase - to - phase: 42; Isolation fracture: 48
    - Lightning Impulse Withstand Voltage (Peak Value) kV To ground, phase - to - phase: 75; Isolation fracture: 85 To ground, phase - to - phase: 75; Isolation fracture: 85
    5 Rated Short - Circuit Withstand Current kA 20 20
    6 Rated Short - Circuit Duration s 4 4
    7 Rated Peak Withstand Current kA 50 50
    8 Rated Effective Load Breaking Current A 630 630
    9 Rated Loop Breaking Current A 630 630
    10 Rated Cable Charging Breaking Current A 10 10
    11 Rated No - Load Transformer Breaking Capacity kVA - 1600
    12 Rated Short - Circuit Breaking Current kA - 31.5
    13 Rated Transfer Current A - 200
    14 Fuse Model - - SDLAJ - 12, SFLAJ - 12
    15 Striker Output Energy J - 1 ± 0.5
    16 Rated Short - Circuit Making Current kA 50 80 (Expected value)
    17 Earthing Switch Rated Short - Time Withstand Current kA - 20
    18 Earthing Switch Rated Short - Circuit Duration s - 2
    19 Earthing Switch Rated Peak Withstand Current kA - 50
    20 Auxiliary Circuit Rated Voltage V ≦ 220 ≦ 110
    21 Mechanical Life Times 10000 10000

    Appearance and installation dimensions

    Frequently Asked Questions (FAQ)

    What are the main applications of the FZN25-12 vacuum load switch?
    It is designed as a control and protection device for three-phase AC 50Hz, 12kV power distribution systems. It is widely used in industrial and mining enterprises, urban building substations, and similar distribution environments.
    What is the difference between the FZN25-12 switch and the FZRN25-12D combination appliance?
    The FZN25-12 is a standard vacuum load switch, whereas the FZRN25-12D is a load switch-fuse combination appliance. The combination appliance offers more reliable short-circuit protection for electrical equipment like transformers compared to standard circuit breakers.
    Can these switches be operated remotely?
    Yes, the opening and closing operation mechanisms are available in both manual and electric versions, facilitating the integration of three-remote control requirements for power systems.
    What safety benefits do these indoor vacuum load switches offer?
    These indoor devices are oil-free, non-toxic, and free from fire and explosion hazards, making them highly safe for indoor installations and compact substations.
    What is the mechanical life span of the FZN25-12 series?
    Both the FZN25-12/T630-20 vacuum load switch and the FZRN25-12D/T200-31.5 combination appliance have a rated mechanical life of 10,000 operations.

    Leave Your Message