China Suppliers Factory KYN28-12 Indoor Metal Enclosed Switchgear for 3-12kV AC Power Distribution
The KYN28-12 (GZSindoor metal armored mid-mounted withdrawable switchgear is a sophisticated solution for three-phase AC 50Hz indoor distribution. This switchgear is specifically designed for receiving and distributing power within 3-12kV network systems. It effectively controls, protects, and monitors electrical circuits, making it a reliable choice for various applications. As a leading product from trusted suppliers in China, this factory-manufactured switchgear ensures high performance and durability, catering to the diverse needs of modern electrical infrastructure
This product's relay chamber panel can be equipped with various types of microcomputer based comprehensive relay protection devices, and can achieve intelligent control of the system. It has remote control, telemetry, remote signaling, and remote adjustment functions, and controls the field network through a CAN bus with a communication interface.
Five Prevention Safety Functions:
Preventing misoperation of circuit breakers.
Preventing pushing handle carts with loads.
Preventing live closing of grounding switches.
Preventing grounding switches from transmitting power in the grounding position.
Preventing accidental entry into live intervals.
Compatible Equipment: Can be equipped with VSI (i.e. ZN63), ZN12V vacuum circuit breakers, as well as imported VD4 vacuum circuit breakers and VC series vacuum contactors.
Environmental Conditions for Use
Temperature & Altitude
Surrounding Air Temperature: Upper limit +40 ℃, lower limit -10 ℃ in general areas.
Altitude: Standard up to 1000m.
Humidity & Water Vapor
Relative Humidity: Daily average ≤ 95%, monthly average ≤ 90%.
Water Vapor Pressure: Daily average ≤ 2.2KPa, monthly average ≤ 1.8KPa.
When the temperature drops sharply, condensation may occur, accompanied by contamination. This product is suitable for the following two environmental conditions that are more severe than normal:
(1). Not frequent condensation (no more than twice a month on average) with mild pollution;
(2). Generally, there is no condensation (no more than twice a year on average) and there is relatively serious pollution;
There is no danger of fire, explosion, or severe pollution that can corrode metals and damage insulation in harsh environments. Suitable for places without severe vibrations, bumps, and vertical inclinations not exceeding 80 degrees.
Notes:
(1) Storage and transportation are allowed at -30 ° C;
(2) When the altitude exceeds 1000m, it shall be handled in accordance with JB/2102 "Technical Requirements for High Voltage Electrical Appliances in High Altitude Areas". When the altitude does not exceed 2000m, no measures need to be taken for low-voltage auxiliary equipment;
(3) When the actual usage conditions differ from the above, both the user and the manufacturer should negotiate.
Schematic Diagram of Switchgear Structure
Compartments & Main Components
A Circuit breaker compartment
B Busbar compartment
C Cable room
D Relay instrument room
1 Busbar
2 Static contact box
3 Circuit breaker
4 Grounding switch
5 Current Transformer
6 Capacitive voltage divider
7 Lightning arrester
Detailed Component Structure
1.1 Pressure relief device
1 Shell
2 Branch small busbar
3 Busbar bushing
4 Main busbar
5 Static contact device
6 Static contact box
7 Current Transformer
8 Grounding switch
9 Cable
10 Lightning arrester
11 Grounding main busbar
12 Loading & unloading partition
13 Partition (valve)
14 Secondary plug
15 Circuit breaker handcart
16 Heater device
17 Removable horizontal partition
18 Grounding switch mechanism
1.2 Control small cable trays
19 Bottom plate
Compliant with Standards
The product meets the following international and national standards:
IEC-298GB3906-1991DL/T404-1997GB/T11022-1999
Frequently Asked Questions
What are the "five prevention" functions of this switchgear?
The "five prevention" features are designed to prevent: 1) misoperation of circuit breakers, 2) pushing handle carts with loads, 3) live closing of grounding switches, 4) grounding switches from transmitting power in the grounding position, and 5) accidental entry into live intervals.
Which types of circuit breakers can be equipped in this cabinet?
This cabinet is highly compatible and can be equipped with VSI (i.e. ZN63), ZN12V vacuum circuit breakers, imported VD4 vacuum circuit breakers, and VC series vacuum contactors.
What are the operating temperature and storage limits?
The standard operating temperature ranges from an upper limit of +40 ℃ to a lower limit of -10 ℃ in general areas. However, safe storage and transportation are permitted at temperatures as low as -30 ° C.
How should the equipment be handled at altitudes exceeding 1000m?
For altitudes above 1000m, handling must follow standard JB/2102 "Technical Requirements for High Voltage Electrical Appliances in High Altitude Areas". Note that if the altitude does not exceed 2000m, no additional measures are required for low-voltage auxiliary equipment.
What are the relative humidity requirements for the installation environment?
The daily average relative humidity should not exceed 95%, and the monthly average should not exceed 90%. Additionally, the daily average water vapor pressure must not exceed 2.2KPa, and the monthly average must not exceed 1.8KPa.