China Suppliers Factory RM6-40.5 SF6 Gas-Insulated Ring Main Unit for 40.5kV Distribution Systems
Overview
BKRM6-40.5 metal ring network switchgear (hereinafter referred to as the inflatable cabinet) is suitable for use in three-phase AC 50Hz, rated voltage 40.5kV distribution systems. It is used for breaking and closing load currents, overload currents, overload currents, and short circuits. It can also disconnect capacitive loads such as no-load transformers, overhead lines at a certain distance, cable lines, and capacitor banks. It plays a role in the distribution, control, and protection of electrical energy in the power system.
BKRM6-40.5 adopts a fully sealed structure, and all primary charged components are sealed in a stainless steel welded chamber with a protection level of IP67. A multi circuit ring network switchgear that can adapt to various harsh environmental conditions such as humidity, salt spray, floods, heavy pollution, etc., and has high operational safety and reliability. Widely used in industrial parks, streets, airports, residential areas, bustling commercial centers, etc., it is an ideal equipment for distribution network automation. It is also used for compact box type substations, cable branch boxes, switch stations, wind power stations, subway and tunnel lights.
BKRM6-40.5 has multiple modules that can be combined according to user requirements, providing multiple combination methods to adapt to the vast majority of situations that require ring network units. Up to 4 modules can be configured in the same SF6 gas chamber. When there are more than 4 units in the module, an extended busbar can be used to connect the switchgear.
Key Advantages
Fully Sealed & Insulated
All live parts are sealed in a 304 stainless steel chamber filled with SF6 gas (1.4 bar, IP67). Ideal for high humidity, dust, mines, and box-type substations.
High Reliability & Safety
Features a pressure relief channel (passed 20kA/0.5s arc test), three-position switches for simplified interlocking, and a reliable mechanical interlock in the cable room.
Maintenance Free
Designed for a 30-year operational lifespan without main switch maintenance. Features an ultra-low annual gas leakage rate of ≤ 0.1%.
Compact Structure
All modules (except air-insulated metering and PT cabinets) are only 500mm wide. Consistent ground height of cable sleeves facilitates easy on-site construction.
Intelligent Control
Equipped with optional intelligent control devices, offering reliable protection, remote control, and monitoring systems for grid automation.
Transformer Protection
Offers two protection methods: load switch fuse combination (for ≤1600kVA transformers) and circuit breakers with relays for various capacities.
Environmental Protection
Uses eco-friendly materials, zero-leakage cleaning technology, and life-sealed construction. 90% to 95% of materials can be recycled post-lifecycle.
Product Parameters
Item |
Unit |
C Module |
F Module |
V Module |
CB Module |
||
|---|---|---|---|---|---|---|---|
(Load Switch) |
(Combined Apparatus) |
(Vacuum Switch) |
Isolation/ |
(Vacuum Circuit Breaker) |
Isolation/ |
||
Rated Voltage |
kV |
36/40.5 |
35/40.5 |
36/40.5 |
36/40.5 |
36/40.5 |
36/40.5 |
Power Frequency Withstand Voltage |
kV |
70/95 |
70/95 |
70/95 |
70/95 |
70/95 |
70/95 |
Isolation Port Voltage |
kV |
80/110 |
80/110 |
80/110 |
|
|
80/110 |
Lightning Impulse Withstand Voltage (Isolation Port) |
kV |
170/185 |
170/185 |
170/185 |
170/185 |
170/185 |
170/185 |
Isolation Port (kV) |
kV |
195/215 |
|
195/215 |
|
|
195/215 |
Rated Current |
A |
630/6301 |
|
200/200 |
|
630/630 |
|
Breaking Capability |
|
|
|
|
|
|
|
Active Load |
A |
630/6330 |
|
200/200 |
|
|
|
Loop Current Breaking |
A |
630/630 |
|
200/200 |
|
|
|
NoLoad Cable Charging |
A |
20/21 |
|
20/21 |
|
50(C1) |
|
Ground Fault |
A |
60/63 |
|
60/63 |
|
|
|
Ground Fault Cable Charging |
A |
35/36 |
|
35/36 |
|
|
|
Transfer Current |
A |
|
|
840/750 |
|
|
|
ShortCircuit Breaking Current |
kA |
|
|
20(Expected) |
|
20/20[EI,S] |
|
Making Capacity |
kA |
50/50 |
|
|
|
|
|
(50 Times) |
|
50/50 |
|
|
|
|
|
(50 Times) |
|
50(Expected) |
2.5/2.5 |
|
|
|
|
(5 Times) |
|
50/50 |
50/50 |
|
|
|
|
Class (Electrical Life) |
|
E3/E2 |
E2/E2 |
/ |
E2/E2 |
E2/E2 |
E2/E2 |
3s ShortTime Withstand Current |
kA |
20/20 |
20/20 |
Limited by HighVoltage Fuse |
|
20/20 |
20/20 |
Internal Arc Classification IAC AFL. 1s |
|
20/20 |
|
20/20 |
|
20/20 |
|
Frequently Asked Questions
Q: What is the rated voltage of the BKRM6-40.5 switchgear?
The BKRM6-40.5 switchgear is designed for three-phase AC 50Hz, rated voltage 40.5kV distribution systems.
Q: What environments is the BKRM6-40.5 suitable for?
Due to its IP67 fully sealed stainless steel welded chamber, it is ideal for harsh environments with high humidity, salt spray, floods, and heavy pollution, such as mines, wind power stations, subways, and tunnels.
Q: Does this switchgear require frequent maintenance?
No. The product features a maintenance-free design with a 30-year lifespan under normal operating conditions, and an annual gas leakage rate of ≤ 0.1%.
Q: How compact is the BKRM6-40.5 switchgear?
Except for the air-insulated metering and PT cabinets, all modules are only 500mm wide, offering a highly compact structure suitable for small installations like box-type substations.
Q: What protection options are available for transformers?
It offers two protection methods: a load switch fuse combination (for transformers of 1600kVA and below) and a circuit breaker with relay protection (suitable for various transformer capacities).
Q: Is the BKRM6-40.5 switchgear environmentally friendly?
Yes, all materials are selected to be eco-friendly, using zero-leakage cleaning technology. It is sealed for life, and 90% to 95% of the materials can be fully recycled at the end of its lifecycle.