China Suppliers Factory RM6-40.5 SF6 Gas-Insulated Ring Main Unit for 40.5kV Distribution Systems
BKRM6-40.5 metal ring network switchgear (hereinafter referred to as the inflatable cabinet) is suitable for use in three-phase AC 50Hz, rated voltage 40.5kV distribution systems. It is used for breaking and closing load currents, overload currents, overload currents, and short circuits. It can also disconnect capacitive loads such as no-load transformers, overhead lines at a certain distance, cable lines, and capacitor banks. It plays a role in the distribution, control, and protection of electrical energy in the power system.
BKRM6-40.5 adopts a fully sealed structure, and all primary charged components are sealed in a stainless steel welded chamber with a protection level of IP67. A multi circuit ring network switchgear that can adapt to various harsh environmental conditions such as humidity, salt spray, floods, heavy pollution, etc., and has high operational safety and reliability. Widely used in industrial parks, streets, airports, residential areas, bustling commercial centers, etc., it is an ideal equipment for distribution network automation. It is also used for compact box type substations, cable branch boxes, switch stations, wind power stations, subway and tunnel lights.
BKRM6-40.5 has multiple modules that can be combined according to user requirements, providing multiple combination methods to adapt to the vast majority of situations that require ring network units Up to 4 modules can be configured in the same SF6 gas chamber. When there are more than 4 units in the module, an extended busbar can be used to connect the switchgear.
All live parts are sealed in a 304 stainless steel box filled with SF6 gas (1.4 bar, IP67). Ideal for mines, box-type substations, and highly polluted or humid environments.
Passed internal fault arc test (20kA/0.5s). Features reliable pressure relief channels and mechanical interlocks between cable room covers and three-position switches.
Designed for a 30-year operational lifespan. The main switch requires no maintenance, maintaining an exceptionally low annual leakage rate of ≤ 0.1%.
Except for metering and PT cabinets, all modules are only 500mm wide. Consistent sleeve ground heights facilitate streamlined and easy on-site construction.
Can be equipped with optional intelligent control devices, providing effective protection, remote control, and monitoring to support power distribution automation.
Developed with eco-friendly processes and materials. Utilizes zero-leakage cleaning technology, and 90% to 95% of the materials can be recycled post-lifecycle.
BKRM6-40.5 provides two protection methods for transformers: load switch fuse combination and circuit breaker with relay protection. Load switch fuse combination devices are used for transformers of 1600kVA and below, while circuit breakers with relays can be used for transformer protection of various capacities.
| Item | Unit | C Module | F Module | V Module | CB Module | ||
|---|---|---|---|---|---|---|---|
| (Load Switch) | (Combined Apparatus) | (Vacuum Switch) | Isolation/ Earthing Switch |
(Vacuum Circuit Breaker) | Isolation/ Earthing Switch |
||
| Rated Voltage | kV | 36/40.5 | 35/40.5 | 36/40.5 | 36/40.5 | 36/40.5 | 36/40.5 |
| Power Frequency Withstand Voltage | kV | 70/95 | 70/95 | 70/95 | 70/95 | 70/95 | 70/95 |
| Isolation Port Voltage | kV | 80/110 | 80/110 | 80/110 | 80/110 | ||
| Lightning Impulse Withstand Voltage (Isolation Port) | kV | 170/185 | 170/185 | 170/185 | 170/185 | 170/185 | 170/185 |
| Isolation Port (kV) | kV | 195/215 | 195/215 | 195/215 | |||
| Rated Current | A | 630/6301 | 200/200 | 630/630 | |||
| Breaking Capability | |||||||
| Active Load | A | 630/6330 | 200/200 | ||||
| Loop Current Breaking | A | 630/630 | 200/200 | ||||
| No-Load Cable Charging | A | 20/21 | 20/21 | 50(C1) | |||
| Ground Fault | A | 60/63 | 60/63 | ||||
| Ground Fault Cable Charging | A | 35/36 | 35/36 | ||||
| Transfer Current | A | 840/750 | |||||
| Short-Circuit Breaking Current | kA | 20(Expected) | 20/20[EI,S] | ||||
| Making Capacity | kA | 50/50 | |||||
| (50 Times) | 50/50 | ||||||
| (5 Times) | 50(Expected) | 2.5/2.5 | |||||
| (5 Times) | 50/50 | 50/50 | |||||
| Class (Electrical Life) | E3/E2 | E2/E2 | / | E2/E2 | E2/E2 | E2/E2 | |
| 3s Short-Time Withstand Current | kA | 20/20 | 20/20 | Limited by High-Voltage Fuse | 20/20 | 20/20 | |
| Internal Arc Classification IAC AFL. 1s | 20/20 | 20/20 | 20/20 | ||||
Q1: What is the rated voltage and application of the BKRM6-40.5 switchgear?
The BKRM6-40.5 is designed for three-phase AC 50Hz distribution systems with a rated voltage of 40.5kV. It is used to distribute, control, and protect electrical energy by breaking and closing load, overload, and short-circuit currents.
Q2: Can this switchgear operate in harsh environmental conditions?
Yes. It features a fully sealed structure with an IP67 protection level. All primary charged components are sealed inside a 304 stainless steel welded chamber filled with SF6 gas, making it highly resistant to humidity, salt spray, floods, and heavy pollution.
Q3: What are the maintenance requirements and expected lifespan of the BKRM6-40.5?
The product is designed to be maintenance-free for its entire 30-year design lifespan. The main switch requires no servicing, and the annual gas leakage rate is kept extremely low at ≤ 0.1%.
Q4: How does the system ensure personal safety during operation?
Safety is ensured through an internal fault arc rating of 20kA/0.5s, reliable pressure relief channels, and three-position switches (load and grounding). Reliable mechanical interlocks between the cable room cover and load switches prevent accidental entry into live sections.
Q5: What options are available for transformer protection?
It offers two main protection methods: a load switch fuse combination (ideal for transformers rated at 1600kVA and below) and a vacuum circuit breaker combined with relay protection (suitable for transformers of various capacities).
Q6: Is the BKRM6-40.5 environmentally friendly?
Yes. The manufacturing process utilizes zero-leakage cleaning technology and eco-friendly materials. Additionally, the unit is sealed for life, and 90% to 95% of its structural materials can be recycled at the end of its lifecycle.