Overview
The operating mechanism and the circuit breaker body are integrated. The design can be used as a fixed installation unit, or can be equipped with a dedicated propulsion mechanism to form a withdrawable unit. The main circuit part can adopt an integrally encapsulated pole to achieve miniaturization, high reliability, and maintenance-free of the circuit breaker. It can be matched with KYN28A - 12(GZS) and other mid-mounted withdrawable switchgear cabinets. The fixed type can also be matched with XGN series fixed switchgear cabinets.
Operating Environment
Ambient Temperature
Not higher than 40°C, and not lower than -10°C (Transportation and storage at -30°C is allowed).
Altitude
Not exceeding 1000m. (If a higher altitude is required, the rated insulation level shall be increased accordingly.)
Relative Humidity
Daily average ≤ 95%, daily average of saturated vapor pressure ≤ 2.2×10⁻³MPa, monthly average ≤ 1.8×10⁻³MPa.
Seismic Intensity
Not exceeding 8 degrees.
Location
No fire, explosion, severe pollution, chemical corrosion, or violent vibration.
Product Parameters
| Item | Description | Unit | Data |
|---|---|---|---|
| 1 | Rated voltage | kV | 24 |
| 2 | Max. voltage | kV | 24 |
| 3 | Rated current | A | 630/1250/2500 |
| 4 | Rated short circuit breaking current | kA | 20/25/31.5 |
| 5 | Rated short circuit making current | kA | 50/63/80 |
| 6 | Rated peak withstand current | kA | 50/63/80 |
| 7 | 4S Rated withstand current | kA | 20/25/31.5 |
| 8 | Rated insulation level - Power frequency voltage (when losing a circuit) | kV | Breaker 85 |
| 8 | Rated insulation level - Impulse withstand voltage (when losing a circuit) | kV | Breaker 125 |
| 9 | Rated operating sequence | - | OC - 0.3s - CO - 180S - CO |
| 10 | Mechanical life | Times | 20000 |
| 11 | Rated short circuit current breaking time | Times | 274 |
| 12 | Rated close brake voltage of operating machine | V | 110, 220 |
| 13 | Rated break brake voltage of operating machine | V | 110, 220 |
| 14 | Contact stroke | mm | 13±1 |
| 15 | Exceed range (the compress length of contact spring) | mm | 3.5±0.5 |
| 16 | Different period of three-phase break and close break | ms | ≤2 |
| 17 | The jump time of contact close break | ms | ≤2 |
| 18 | Average break speed | m/s | 1.1 - 1.7 |
| 19 | Average closing speed | m/s | 0.6 - 1.1 |
| 20 | Opening time - Under max. operating voltage | S | ≤0.05 |
| 20 | Opening time - Under min. operating voltage | S | ≤0.08 |
| 21 | Closing time | s | 0.1 |
| 22 | Resistance of each phase main loop | μΩ | 830≤50; 1250≤45; 1600 - 2500≤40 |
| 23 | Contacts limit erosion | mm | 3 |
Frequently Asked Questions
What are the compatible switchgear cabinets for this circuit breaker?
The withdrawable unit type matches KYN28A-12(GZS) and other mid-mounted withdrawable switchgear cabinets. The fixed type is compatible with XGN series fixed switchgear cabinets.
What is the operating temperature range allowed for installation?
The standard ambient operating temperature should not be higher than 40°C and not lower than -10°C. However, transportation and storage are allowed at temperatures as low as -30°C.
Can this circuit breaker be installed at altitudes higher than 1000m?
The standard design is rated for altitudes up to 1000m. For installations at higher altitudes, the rated insulation level of the equipment must be increased accordingly.
What is the rated mechanical life of this unit?
This circuit breaker features a robust mechanical design with a rated mechanical life of up to 20,000 operations.
What environmental conditions should be avoided for installation?
The equipment should be installed in locations free from risk of fire, explosion, severe environmental pollution, chemical corrosion, or violent physical vibrations.