China VS1 Vacuum Circuit Breaker Factory - 12kV Indoor High Voltage Circuit Breakers Suppliers for Industrial Applications
Overview
The operating mechanism and the circuit breaker body are integrated. The design can be used as a fixed installation unit, or can be equipped with a dedicated propulsion mechanism to form a withdrawable unit. The main circuit part can adopt an integrally encapsulated pole to achieve miniaturization, high reliability, and maintenance-free of the circuit breaker. It can be matched with KYN28A - 12(GZS) and other mid-mounted withdrawable switchgear cabinets. The fixed type can also be matched with XGN series fixed switchgear cabinets.
Operating Environment
Ambient Temperature
Not higher than 40°C, and not lower than -10°C (Transportation and storage at -30°C is allowed).
Altitude
Not exceeding 1000m. (If a higher altitude is required, the rated insulation level shall be increased accordingly.)
Relative Humidity
Daily average ≤ 95% (saturated vapor pressure ≤ 2.2×10¹&sup0; MPa), monthly average ≤ 90% (saturated vapor pressure ≤ 1.8×10¹&sup0; MPa).
Seismic Intensity
Not exceeding 8 degrees.
Location Requirements
No fire, explosion, severe pollution, chemical corrosion, or violent vibration.
Product Parameters
| Item | Description | Unit | Data |
|---|---|---|---|
| 1 | Rated voltage | kV | 24 |
| 2 | Max. voltage | kV | 24 |
| 3 | Rated current | A | 630/1250/2500 |
| 4 | Rated short circuit breaking current | kA | 20/25/31.5 |
| 5 | Rated short circuit making current | kA | 50/63/80 |
| 6 | Rated peak withstand current | kA | 50/63/80 |
| 7 | 4S Rated withstand current | kA | 20/25/31.5 |
| 8 | Rated insulation level - Power frequency voltage(when losing a circuit) | kV | Dreaker 85 |
| 8 | Rated insulation level - Impulse withstand voltage(when losing a circuit) | kV | Dreaker 125 |
| 9 | Rated operating sequence | - | OC - 0.3s - CO - 180S - CO |
| 10 | Mechanical life | Times | 20000 |
| 11 | Rated short circuit current breaking time | Times | 274 |
| 12 | Rated close brake voltage of operating machine | V | 110,220 |
| 13 | Rated break brake voltage of operating machine | V | 110,220 |
| 14 | Contact stroke | mm | 13±1 |
| 15 | Exceed range(the compress length of contact spring) | mm | 3.5±0.5 |
| 16 | Different period of three - phase break and close break | ms | ≤2 |
| 17 | The jump time of contact close break | ms | ≤2 |
| 18 | Average break speed | m/s | 1.1 - 1.7 |
| 19 | Average closing speed | m/s | 0.6 - 1.1 |
| 20 | Opening time - Under max. operating voltage | S | ≤0.05 |
| 20 | Opening time - Under min. operating voltage | S | ≤0.08 |
| 21 | Closing time | s | 0.1 |
| 22 | Resistance of each phase main loop | μΩ | 830≤50;1250≤45;1600 - 2500≤40 |
| 23 | Contacts limit erosion | mm | 3 |
Frequently Asked Questions
Q: What switchgear cabinets are compatible with this circuit breaker?
The withdrawable unit configuration is compatible with KYN28A-12(GZS) and other mid-mounted withdrawable switchgear cabinets. The fixed type unit is designed to match XGN series fixed switchgear cabinets.
Q: What is the mechanical service life of the operating mechanism?
This integrated circuit breaker features a robust mechanical design rated for a mechanical life of up to 20,000 operations, ensuring long-term reliability and low maintenance requirements.
Q: Can this circuit breaker be installed in high-altitude environments?
The standard design is rated for altitudes up to 1000 meters. If your application requires installation at a higher altitude, the rated insulation level must be increased accordingly to ensure safe operation.
Q: What are the ambient temperature limits for safe operation?
The operating ambient temperature should remain between -10°C and 40°C. However, the unit is durable enough to withstand transportation and storage conditions down to -30°C.
Q: What is the rated short-circuit breaking capacity?
Depending on the specific model configuration selected, the rated short-circuit breaking current options are 20 kA, 25 kA, or 31.5 kA.