China XGN15 Series Fixed Metal-Enclosed Ring Main Unit - Reliable RMU Suppliers and Factory for 12kV Power Distribution
Overview
In terms of application, it is widely used in urban distribution networks, industrial and mining enterprises, commercial buildings, and residential communities. For example, in urban distribution networks, it can be used to construct ring - shaped power supply networks, enabling flexible power supply and quick fault isolation. In industrial and mining enterprises, it ensures the stable power supply for production equipment, and in commercial buildings and residential communities, it meets the power demand for daily electricity consumption and various electrical appliances.
Environmental Conditions
Altitude ≤ 1000m. (Special requirements can be specified when ordering);
Environmental temperature: -25 ℃~+40 ℃;
The average daily relative humidity does not exceed 95%; The average monthly relative humidity does not exceed 90%;
Seismic resistance: 8 degrees;
Places without severe vibration and impact, as well as places with fire, chemical corrosion, and explosion hazards.
Structural Design Features
Compact Modular Architecture
Adopts unitized, modular design with CNC-machined steel cabinets. Clear compartment separation (busbar, cable, and operating mechanism chambers) minimizes footprint, ideal for urban substations and small distribution rooms.
Enhanced Enclosure Protection
IP3X-rated housing prevents dust ingress and accidental contact. Air-insulated or SF₆-insulated (optional) design shields live parts from moisture and corrosive environments, ensuring long-term reliability.
Fail-Safe Interlocking System
Mechanical interlocks enforce "Five-Prevention" protocols:
- Prevent accidental breaker operation.
- Block load switching of disconnectors.
- Avoid grounding with live circuits.
- Prevent closing on grounded circuits.
- Restrict entry to live compartments.
Electrical Performance Features
High Breaking Capacity
Main switches (SF₆ load switches or vacuum circuit breakers) offer rapid arc extinction, short arcing time, and fast dielectric recovery. Capable of interrupting low inductive/capacitive currents and short-circuit faults (e.g., 20kA for 3s), minimizing outage scope.
Wide Parameter Compatibility
Rated for 12kV systems with 630A current, 20kA short-time withstand current, and 50kA peak withstand current. Optimized for 10-12kV distribution networks, supporting reliable power allocation.
Flexible Component Integration
Configurable with domestic SF₆ load switches (e.g., FLN36 series) or vacuum circuit breakers (e.g., VD4-S). Compatible with fuses, CTs/PTs, and transformer protection modules for tailored solutions.
Product Parameters
| Item | Unit | Parameter | ||
|---|---|---|---|---|
| XGN15-12(F) | XGN15-12(F.R) | |||
| Rated voltage | kV | 12 | ||
| Rated frequency | Hz | 50 | ||
| Rated insulation level | 1min power - frequency withstand voltage | kV | 42 for ground and phase - to -phase; 48 for isolation break |
|
| Lightning impulse withstand voltage (peak value) | kV | 75 for ground and phase - to -phase; 85 for isolation break |
||
| Rated current of main busbar | A | 630 | ||
| Rated current | A | 630 | 125 | |
| Rated closed - loop breaking current | A | 630 | - | |
| Rated active load breaking current | A | 630 | - | |
| Rated charging breaking current | A | 10 | - | |
| Rated transfer current | A | - | 1700 | |
| Breaking capacity of no- load transformer | kVA | 1600 | ||
| Rated making current (peak value) | kA | 63 | - | |
| Rated short- time withstand current(2S) | kA | 25 | - | |
| Rated peak withstandcurrent | kA | 63 | - | |
| Rated short- circuit breaking current | kA | - | - | |
| Peak withstand current of grounding circuit | kA | 63 | 31.5 (expected) | |
| Short-time withstand current of grounding circuit (2S) | kA | 25 | - | |
| Type of matching fuse | - | - | S口LAJ | |
| Rated voltage of auxiliary circuit | V | DC220,110,AC220,110 | ||
| Protection level | - | IP3X | ||
| Mechanical life | Load switch | times | 5000 | |
| Grounding switch | times | 2000 | ||
Frequently Asked Questions
QWhat are the main applications of the XGN15-12 switchgear?
The XGN15-12 switchgear is widely used in urban distribution networks (for ring power networks), industrial and mining enterprises, commercial buildings, and residential communities to ensure stable power supply and enable quick fault isolation.
QWhat are the environmental limits for installing this equipment?
It is designed for altitudes ≤ 1000m, operating temperatures between -25 ℃ and +40 ℃, and a daily relative humidity not exceeding 95% (monthly ≤ 90%). It has a seismic resistance rating of 8 degrees and should be installed away from severe vibrations, chemical corrosion, or fire hazards.
QWhat mechanical interlocks are included in the "Five-Prevention" system?
The fail-safe interlocking system prevents: accidental breaker operation, load switching of disconnectors, grounding with live circuits, closing on grounded circuits, and unauthorized entry to live compartments.
QWhat is the protection level of the enclosure?
The switchgear cabinet features an IP3X-rated housing that prevents dust ingress and accidental physical contact with live internal components, ensuring high operational safety.
QCan I configure this switchgear with different breakers?
Yes. The modular design supports flexible component integration, allowing configuration with domestic SF₆ load switches (such as the FLN36 series) or vacuum circuit breakers (such as the VD4-S), along with fuses and CTs/PTs.
QWhat is the difference in rated current between the F and F.R models?
According to the parameters, the XGN15-12(F) model is rated for 630A, while the XGN15-12(F.R) model is rated for 125A and matches with a specific fuse type (S口LAJ).