Leave Your Message
Products Categories
Featured Products

China ZW32-12 Outdoor Medium Voltage Vacuum Circuit Breaker Suppliers & Factory for Power Distribution Solutions

The ZW32-12 outdoor high voltage vacuum circuit breaker is an advanced distribution solution designed for a rated voltage of 12kV and a three-phase AC frequency of 50Hz. As a reliable product from a leading manufacturer in China, this circuit breaker is essential for effectively managing load currents, overload currents, and short circuit currents within power systems. Ideal for the protection and control of power distribution systems in substations and industrial enterprises, it is particularly well-suited for rural power grids that require frequent operation. This vacuum circuit breaker boasts a compact design and lightweight construction, making it easy to install and maintain. Its anti-condensation features ensure optimal performance in harsh weather and dirty environments, which is a key advantage for suppliers and industries needing durable equipment. Choose our ZW32-12 circuit breaker for your next project and benefit from its low maintenance requirements and robust reliability, hallmarks of our factory's commitment to quality and innovation.

    Overview

    ZW32-12 outdoor high voltage vacuum circuit breaker (hereinafter referred to as circuit breaker) is outdoor distribution equipment with rated voltage of 12kV and three-phase AC of 50Hz. It is mainly used to open and close load current, overload current and short circuit current in power system. It is suitable for the protection and control in the power distribution system of substation and industrial and mining enterprises, as well as the places where the rural power grid is frequently operated. The circuit breaker has the characteristics of small volume, lightweight, anti-condensation, free maintenance and so on. It can adapt to the harsh weather conditions and a dirty environments.

    Model and Meaning

    1.1.ZW32 Series Outdoor Three Phase Medium Voltage Vacuum Circuit Breaker.png

    Working Conditions

    Environment Temperature: Upper limit +40°C, lower limit -30°C
    Altitude: ≤ 2000 meters
    Wind Pressure: No more than 700Pa (wind speed 34m/s)
    Earthquake Intensity: Do not exceed 8 degree
    Pollution Grade: Class I
    Daily Temperature: Maximum difference less than 25°C

    Technical Parameters

    Name Unit Data
    Rated Voltage kV 12
    Rated Insulation Level 1min Power Frequency Withstand Voltage Dry Test (To Ground, Pole-to-Pole / Break) kV 42/48
    Wet Test 34
    Lightning Impulse Withstand Voltage (Peak Value, Pole-to-Pole / Break) kV 75/85
    Rated Current A 630
    Rated Short-Circuit Breaking Current kA 20
    Rated Operating Sequence - O~0.3-CO-180S-COS
    Rated Short-Circuit Breaking Current Breaking Times Times 30
    Rated Short-Circuit Making Current (Peak Value) kA 50
    Rated Peak Withstand Current kA 50
    Rated Short-Time Withstand Current kA 20
    Rated Short-Circuit Duration Time S 4
    Opening Time ms ≤35
    Closing Time ms ≤40
    Mechanical Life Times 10000
    Rated Closing Operation Voltage V DC110
    Rated Opening Operation Voltage
    Overcurrent Protection Current Setting Multiple - 0.2~2.5
    Allowable Deviation of Setting Current % ±10%
    Delay Setting Value S 0~5
    Delay Tolerance % ±10%
    Instantaneous Trip Protection Current Setting Multiple - 2.5~10
    Allowable Deviation of Setting Current % ±10%
    Delay Setting Value S 0~0.5
    Delay Tolerance % ±10%
    AC Charging Input Current of Control Unit Rated Value A 5
    Fluctuation Range 0.5~8

    Product Size Description

    Frequently Asked Questions (FAQ)

    1. What is the main application of the ZW32-12 vacuum circuit breaker?

    The ZW32-12 is primarily designed for outdoor 12kV, 50Hz medium voltage distribution systems. It is utilized to open and close load current, overload current, and short circuit current in electrical substations, industrial power lines, and rural power networks.

    2. What are the key environmental operational limits for this equipment?

    It operates under ambient temperatures ranging from -30°C to +40°C, an altitude up to 2000 meters, maximum wind pressures up to 700Pa (approx. 34 m/s), and withstands earthquake conditions up to magnitude 8.

    3. What is the mechanical service life of the ZW32-12?

    The circuit breaker features an enduring mechanical life of up to 10,000 operations, offering robust reliability and free maintenance for extended utility cycles.

    4. What is the breaking capacity of the circuit breaker during a short circuit?

    The device possesses a rated short-circuit breaking current of 20kA and can endure up to 30 operations at its rated short-circuit breaking current capacity.

    5. What protection functions are integrated into the unit?

    The unit integrates overcurrent protection (current setting multiple of 0.2~2.5) and instantaneous trip protection (current setting multiple of 2.5~10) with adjustable delay time settings for secure power network operations.