China ZW32-12 Outdoor Three Phase Medium Voltage Vacuum Circuit Breaker - Suppliers & Factory Direct Offer
Overview
ZW32-12 outdoor high voltage vacuum circuit breaker (hereinafter referred to as circuit breaker) is outdoor distribution equipment with rated voltage of 12kV and three-phase AC of 50Hz. It is mainly used to open and close load current, overload current and short circuit current in power system. It is suitable for the protection and control in the power distribution system of substation and industrial and mining enterprises, as well as the places where the rural power grid is frequently operated. The circuit breaker has the characteristics of small volume, lightweight, anti-condensation, free maintenance and so on. It can adapt to the harsh weather conditions and a dirty environments.
Model and Meaning
Working Conditions
-
1. The environment temperature: upper limit +40℃, lower limit -30℃
-
2. Altitude ≤ 2000 meters
-
3. Wind pressure: no more than 700Pa (corresponding to the wind speed 34m/s)
-
4. Earthquake intensity: do not exceed 8 degree
-
5. Pollution grade: I class
-
6. Maximum daily temperature: less than 25℃.
Technical parameters
| Name | Unit | Data | ||
|---|---|---|---|---|
| Rated Voltage | kV | 12 | ||
| Rated Insulation Level | 1min Power Frequency Withstand Voltage | Dry Test (To Ground, Pole-to-Pole / Break) | 42/48 | |
| Wet Test | 34 | |||
| Lightning Impulse Withstand Voltage (Peak Value, Pole-to-Pole / Break) | 75/85 | |||
| Rated Current | A | 630 | ||
| Rated Short-Circuit Breaking Current | kA | 20 | ||
| Rated operating sequence | O~0.3-CO-180S-COS | |||
| Rated short-circuit breaking current breaking times | Times | 30 | ||
| Rated Short-Circuit Making Current (Peak Value) | kA | 50 | ||
| Rated Peak Withstand Current | ||||
| Rated Short-Time Withstand Current | 20 | |||
| Rated Short-Circuit Duration time | S | 4 | ||
| Opening Time | ms | ≤35 | ||
| Closing Time | ms | ≤40 | ||
| Mechanical Life | Times | 10000 | ||
| Rated Closing Operation Voltage | V | DC110 | ||
| Rated Opening Operation Voltage | ||||
| Overcurrent Protection | Current Setting Multiple | 0.2~2.5 | ||
| Allowable deviation of setting current | ±10% | |||
| Delay Setting Value | S | 0~5 | ||
| Delay Tolerance | ±10% | |||
| Instantaneous Trip Protection | Current Setting Multiple | 2.5~10 | ||
| Allowable deviation of setting current | ±10% | |||
| Delay Setting Value | S | 0~0.5 | ||
| Delay Tolerance | ±10% | |||
| AC Charging Input Current of Control Unit | Rated Value | A | 5 | |
| Fluctuation Range | 0.5~8 | |||
PRODUCT SIZE DESCRIPTION
FAQ
The ZW32-12 outdoor high voltage vacuum circuit breaker is designed for power distribution systems with a rated voltage of 12kV and a three-phase AC frequency of 50Hz.
It is primarily used to open and close load currents, overload currents, and short-circuit currents. It is widely applied for protection and control in substations, industrial and mining enterprises, and frequently operated rural power grids.
The equipment operates reliably within an environmental temperature range from a lower limit of -30℃ to an upper limit of +40℃.
Yes, it features anti-condensation, small volume, light weight, and maintenance-free characteristics, allowing it to adapt to harsh weather conditions and dirty operating environments.
The ZW32-12 outdoor high voltage vacuum circuit breaker has a mechanical life rating of 10,000 times.
The standard working conditions allow for installation and operation at an altitude of up to 2000 meters.