CKSG Low Voltage Three-Phase Reactor - China Suppliers & Factory for Reactive Power Compensation Solutions

The CKSG low-voltage three-phase reactor is an essential component for low-voltage reactive power compensation systems, specifically designed for AC 50Hz power networks with rated voltages ranging from 6 to 35kV, including common low-voltage ratings such as 0.4kV. This reactor effectively works in series with low-voltage capacitors to mitigate issues such as harmonic currents, inrush currents during switching, and operating overvoltages. By doing so, it protects capacitors from damage and enhances the overall power factor, Additionally, the CKSG reactor plays a vital role in harmonics absorption, improving power quality, ensuring stable system operation, and extending the lifespan of capacitors. Manufactured with a dry-type iron-core structure and utilizing advanced processes like vacuum pressure impregnation, this product guarantees superior performance. As a leading supplier and factory in China, we are dedicated to providing high-quality reactors that meet global standards and client requirements

    Overview

    The CKSG low-voltage three-phase reactor is a supporting device for low-voltage reactive power compensation installations. It is suitable for AC 50Hz power systems with a rated voltage of 6 - 35kV (common low-voltage ratings include 0.4kV, etc.). When connected in series with low-voltage capacitors, it can suppress harmonic currents, inrush currents during switching, and operating overvoltages, preventing damage to capacitors and a reduction in the power factor. Additionally, it can absorb harmonics, improve power quality, facilitate the stable operation of the system, and extend the service life of capacitors. It mostly adopts a dry-type iron-core structure, and processes such as vacuum pressure impregnation are used to ensure performance.

    Product Features

    1. Harmonic & Inrush Current Suppression

    Suppresses harmonic currents (THDi ≤ 10% per GB/T 14549) and inrush currents during capacitor switching, preventing insulation breakdown of capacitors.

    Mitigates switching overvoltages to maintain power factor stability (≥0.95) in low-voltage systems.

    2. Power Quality Optimization

    Absorbs dominant harmonics (5th, 7th, etc.) to reduce voltage total harmonic distortion (THDu ≤ 5%).

    Stabilizes bus voltage fluctuations, ensuring compliance with GB/T 12325 for voltage quality.

    3. Dry-Type Core Structure

    Adopts laminated silicon steel core with low eddy current loss (≤0.3W/kg at 1.7T, 50Hz).

    Vacuum Pressure Impregnation (VPI) process enhances insulation strength (dielectric withstand voltage ≥3kV) and moisture resistance (IP20 protection).

    4. System Synergy with Capacitors

    Forms LC filtering loops with BSMJ-series capacitors, reducing reactive power loss by 30-40%.

    Supports stepwise compensation configurations (10-500kvar) for scalable reactive power control.

    5. Reliability & Longevity

    Temperature rise ≤65K under rated load, ensuring continuous operation at -25℃~+45℃.

    Built-in thermal protection triggers alarm at core temperature >130℃ (Class B insulation).

    6. Installation Flexibility

    Vertical/horizontal mounting compatible with standard low-voltage switchgear (e.g., GGD, GCK cabinets).

    Low noise design (≤55dB at 1m) suitable for indoor power distribution rooms.

    7. Compliance with Standards

    Meets JB/T 9644 (dry-type reactor technical specifications) and IEC 60289 for reactor performance.

    Product Parameters

    Three-Phase Reactor Parameters (CKSG Series)
    Reactor model Matching capacitor capacity (kvar) Reactor capacity (kvar) Inductance (mH) Insulation class Dimensions D*W*H (mm) Installation size (mm)
    CKSG-0.35/0.45-7% 5 0.35 9 F、H 170*100*160 150*60
    CKSG-0.7/0.45-7% 10 0.7 4.5 F、H 175*110*160 150*70
    CKSG-1.05/0.45-7% 15 1.05 3 F、H 175*145*160 150*80
    CKSG-1.4/0.45-7% 20 1.4 2.3 F、H 200*155*185 170*80
    CKSG-1.75/0.45-7% 25 1.75 1.8 F、H 240*165*210 200*90
    CKSG-2.1/0.45-7% 30 2.1 1.5 F、H 240*170*210 200*95
    CKSG-2.45/0.45-7% 35 2.45 1.3 F、H 240*175*210 200*100
    CKSG-2.8/0.45-7% 40 2.8 1.1 F、H 240*180*210 210*105
    CKSG-3.15/0.45-7% 45 3.15 1 F、H 240*190*210 200*110
    CKSG-3.5/0.45-7% 50 3.5 0.9 F、H 250*190*210 210*110
    CKSG-4.2/0.45-7% 60 4.2 0.75 F、H 250*190*250 210*120
    CKSG-1.4/0.525-14% 10 1.4 12.3 F、H 200*120*190 170*80
    CKSG-2.1/0.525-14% 15 2.1 8.2 F、H 240*165*210 200*95
    CKSG-2.8/0.525-14% 20 2.8 6.1 F、H 240*175*210 200*105
    CKSG-3.5/0.525-14% 25 3.5 4.9 F、H 240*185*240 200*110
    CKSG-4.2/0.525-14% 30 4.2 4.1 F; H 250*185*250 210*110
    CKSG-5.6/0.525-14% 40 5.6 3.1 F; H 250*190*265 210*115
    CKSG-7.0/0.525-14% 50 7 2.5 F; H 310*200*285 260*120
    Single-Phase Reactor Parameters (CKDG Series)
    Reactor model Matching capacitor capacity (kvar) Reactor capacity (kvar) Inductance (mH) Dimensions D*W*H (mm) Installation size (mm)
    CKDG-0.35/0.25-7% 5 0.35 2.8 135*155*140 95×105.4-φ8
    CKDG-0.525/0.25-7% 7.5 0.525 1.9 135*165*155 95×105.4-φ8
    CKDG-0.7/0.25-7% 10 0.7 1.4 170*175*160 120×115.4-φ8
    CKDG-1.05/0.25-7% 15 1.05 0.93 170*195*180 120×135.4-φ8
    CKDG-1.4/0.25-7% 20 1.4 0.7 155*195*210 105×135.4-φ8
    CKDG-1.75/0.25-7% 25 1.75 0.56 155*205*210 105×145.4-φ8

    Frequently Asked Questions (FAQ)

    What is the primary function of the CKSG low-voltage reactor?
    The CKSG low-voltage reactor is connected in series with low-voltage capacitors to suppress harmonic currents, reduce switching inrush currents, and mitigate operating overvoltages. This prevents capacitor damage and maintains a stable system power factor.
    What insulation classes do the CKSG and CKDG reactors support?
    These reactors feature high-performance Class F and Class H insulation, designed to withstand demanding thermal conditions and ensure long-term operational reliability.
    How does the VPI process improve the reactor's performance?
    The Vacuum Pressure Impregnation (VPI) process enhances the insulation strength of the dry-type iron core, resulting in a dielectric withstand voltage of ≥3kV and superior moisture resistance rated at IP20 protection.
    Does the reactor include built-in thermal protection?
    Yes, it features a built-in thermal protection mechanism that triggers an alarm if the core temperature exceeds 130°C, preventing thermal overload and potential damage.
    What mounting options are available for installation?
    The reactors are designed for installation flexibility, supporting both vertical and horizontal mounting configurations. They are fully compatible with standard low-voltage switchgear cabinets such as GGD and GCK.
    Which industry standards do these reactors comply with?
    They fully comply with JB/T 9644 (technical specifications for dry-type reactors) and IEC 60289 international standards for reactor performance and safety.