CKSG Low Voltage Three-Phase Reactor from China Suppliers - Quality Factory Solution for Reactive Power Compensation
Harmonic & Inrush Current Suppression
- Suppresses harmonic currents (THDi ≤ 10% per GB/T 14549) and inrush currents during capacitor switching, preventing insulation breakdown of capacitors.
- Mitigates switching overvoltages to maintain power factor stability (≥0.95) in low-voltage systems.
Power Quality Optimization
- Absorbs dominant harmonics (5th, 7th, etc.) to reduce voltage total harmonic distortion (THDu ≤ 5%).
- Stabilizes bus voltage fluctuations, ensuring compliance with GB/T 12325 for voltage quality.
Dry-Type Core Structure
- Adopts laminated silicon steel core with low eddy current loss (≤0.3W/kg at 1.7T, 50Hz).
- Vacuum Pressure Impregnation (VPI) process enhances insulation strength (dielectric withstand voltage ≥3kV) and moisture resistance (IP20 protection).
System Synergy with Capacitors
- Forms LC filtering loops with BSMJ-series capacitors, reducing reactive power loss by 30-40%.
- Supports stepwise compensation configurations (10-500kvar) for scalable reactive power control.
Reliability & Longevity
- Temperature rise ≤65K under rated load, ensuring continuous operation at -25℃~+45℃.
- Built-in thermal protection triggers alarm at core temperature >130℃ (Class B insulation).
Installation Flexibility
- Vertical/horizontal mounting compatible with standard low-voltage switchgear (e.g., GGD, GCK cabinets).
- Low noise design (≤55dB at 1m) suitable for indoor power distribution rooms.
Compliance with Standards
- Meets JB/T 9644 (dry-type reactor technical specifications) and IEC 60289 for reactor performance.
| Reactor model | Matching capacitor capacity (kvar) | Reactor capacity (kvar) | Inductance (mH) | Insulation class | Dimensions D*W*H (mm) | Installation size (mm) |
|---|---|---|---|---|---|---|
| CKSG-0.35/0.45-7% | 5 | 0.35 | 9 | F、H | 170*100*160 | 150*60 |
| CKSG-0.7/0.45-7% | 10 | 0.7 | 4.5 | F、H | 175*110*160 | 150*70 |
| CKSG-1.05/0.45-7% | 15 | 1.05 | 3 | F、H | 175*145*160 | 150*80 |
| CKSG-1.4/0.45-7% | 20 | 1.4 | 2.3 | F、H | 200*155*185 | 170*80 |
| CKSG-1.75/0.45-7% | 25 | 1.75 | 1.8 | F、H | 240*165*210 | 200*90 |
| CKSG-2.1/0.45-7% | 30 | 2.1 | 1.5 | F、H | 240*170*210 | 200*95 |
| CKSG-2.45/0.45-7% | 35 | 2.45 | 1.3 | F、H | 240*175*210 | 200*100 |
| CKSG-2.8/0.45-7% | 40 | 2.8 | 1.1 | F、H | 240*180*210 | 210*105 |
| CKSG-3.15/0.45-7% | 45 | 3.15 | 1 | F、H | 240*190*210 | 200*110 |
| CKSG-3.5/0.45-7% | 50 | 3.5 | 0.9 | F、H | 250*190*210 | 210*110 |
| CKSG-4.2/0.45-7% | 60 | 4.2 | 0.75 | F、H | 250*190*250 | 210*120 |
| CKSG-1.4/0.525-14% | 10 | 1.4 | 12.3 | F、H | 200*120*190 | 170*80 |
| CKSG-2.1/0.525-14% | 15 | 2.1 | 8.2 | F、H | 240*165*210 | 200*95 |
| CKSG-2.8/0.525-14% | 20 | 2.8 | 6.1 | F、H | 240*175*210 | 200*105 |
| CKSG-3.5/0.525-14% | 25 | 3.5 | 4.9 | F、H | 240*185*240 | 200*110 |
| CKSG-4.2/0.525-14% | 30 | 4.2 | 4.1 | F、H | 250*185*250 | 210*110 |
| CKSG-5.6/0.525-14% | 40 | 5.6 | 3.1 | F、H | 250*190*265 | 210*115 |
| CKSG-7.0/0.525-14% | 50 | 7 | 2.5 | F、H | 310*200*285 | 260*120 |
| Reactor model | Matching capacitor capacity (kvar) | Reactor capacity (kvar) | Inductance (mH) | Dimensions D*W*H (mm) | Installation size (mm) |
|---|---|---|---|---|---|
| CKDG-0.35/0.25-7% | 5 | 0.35 | 2.8 | 135*155*140 | 95×105.4-φ8 |
| CKDG-0.525/0.25-7% | 7.5 | 0.525 | 1.9 | 135*165*155 | 95×105.4-φ8 |
| CKDG-0.7/0.25-7% | 10 | 0.7 | 1.4 | 170*175*160 | 120×115.4-φ8 |
| CKDG-1.05/0.25-7% | 15 | 1.05 | 0.93 | 170*195*180 | 120×135.4-φ8 |
| CKDG-1.4/0.25-7% | 20 | 1.4 | 0.7 | 155*195*210 | 105×135.4-φ8 |
| CKDG-1.75/0.25-7% | 25 | 1.75 | 0.56 | 155*205*210 | 105×145.4-φ8 |
The CKSG low-voltage series reactor is designed to suppress harmonic currents and inrush currents during capacitor switching. It mitigates operating overvoltages, prevents capacitor damage, and helps maintain a stable power factor in reactive power compensation systems.
The Vacuum Pressure Impregnation (VPI) process enhances the insulation strength of the dry-type core structure, giving it a dielectric withstand voltage of ≥3kV. It also increases moisture resistance, ensuring high reliability and a long service life.
The reactors comply with the JB/T 9644 standard (dry-type reactor technical specifications) and the IEC 60289 international standard for reactor performance.
They feature flexible vertical or horizontal mounting and are fully compatible with standard low-voltage switchgear cabinets such as GGD and GCK cabinets. Their low-noise design (≤55dB at 1m) makes them ideal for indoor power distribution rooms.
Yes, it features Class B insulation with built-in thermal protection that triggers an alarm if the core temperature exceeds 130°C, ensuring safe operation within a -25°C to +45°C temperature range.