Energy-Saving SC (B) 11 Dry-Type Power Transformer 6KV/10KV - China Suppliers & Factory Solutions
The no-load loss has decreased by about 12%, making it more energy-efficient and environmentally friendly. Long term operation can save more electricity costs, improve economic efficiency, and meet the current development needs of energy conservation and consumption reduction.
Higher mechanical strength, better short-circuit resistance, less likely to be damaged in the face of short-circuit faults, and improved operational reliability; High insulation level and good lightning impulse resistance, which can better protect equipment and reduce the probability of failure under overvoltage conditions such as lightning.
The maintenance free feature is more prominent, with excellent moisture-proof performance. It can operate in a 100% humidity environment without preheating before operation, and intermittent operation does not require dehumidification treatment, reducing operation and maintenance costs and workload.
Small in size, lightweight, easy to transport and install, can save installation space; Reduced noise level, quieter operation, and reduced noise interference to the surrounding environment.
With strong heat dissipation capabilities, it can achieve 150% rated load operation under cold air conditions, ensuring stable power supply during short-term load peaks and improving equipment applicability and flexibility.
| Rated Capacity kVA | Voltage Combination kV | Connection Symbol | No-load Loss kW | Load Loss W | No-load Current A | Short-circuit Impedance % | Weight kg | Outer Dimensions mm (L×B×H) | Rail Gauge | |||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| High Voltage | Low Voltage | Tank Body | Oil Weight | Total Weight | ||||||||
| 200 | 10.5 10 6.3 6 |
6.3 3.15 3 |
Yd11 Dy11 |
0.340 | 3.15 | 1.8 | 4.5 | 650 | 160 | 1000 | 1180×740×1270 | 660/660 |
| 250 | 0.400 | 3.60 | 1.7 | 770 | 200 | 1190 | 1230×780×1340 | |||||
| 315 | 0.480 | 4.30 | 1.6 | 900 | 215 | 1360 | 1260×810×1370 | |||||
| 400 | 0.570 | 5.20 | 1.5 | 1080 | 260 | 1650 | 1380×900×1390 | |||||
| 500 | 0.680 | 6.20 | 1.4 | 1250 | 280 | 1890 | 1400×920×1450 | |||||
| 630 | 0.820 | 6.92 | 0.6 | 5.5 | 1470 | 340 | 340 | 1580×1020×1430 | 820/820 | |||
| 800 | 1.000 | 8.46 | 0.6 | 1735 | 385 | 2645 | 1665×1070×1520 | |||||
| 1000 | 1.180 | 9.91 | 0.6 | 1910 | 430 | 2980 | 1740×1160×1550 | |||||
| 1250 | 1.400 | 11.70 | 0.5 | 2210 | 590 | 3640 | 1820×1210×1740 | |||||
| 1600 | 1.680 | 14.10 | 0.4 | 2640 | 680 | 4270 | 1840×1240×1860 | |||||
| 2000 | 2.010 | 16.90 | 0.4 | 2890 | 725 | 4775 | 2210×1920×1970 | |||||
| 2500 | 2.370 | 19.60 | 0.4 | 3460 | 910 | 5710 | 2260×1970×1995 | 1070/1070 | ||||
| 3150 | 2.800 | 23.00 | 0.4 | 4230 | 1350 | 7085 | 2320×2280×2360 | |||||
| 4000 | 10.5 10 |
6.3 3.15 |
3.450 | 27.30 | 0.4 | 5025 | 1675 | 8150 | 2460×2480×2475 | |||
| 5000 | 4.100 | 31.30 | 0.4 | 6020 | 1940 | 9610 | 2575×2640×2590 | |||||
| 6300 | 4.890 | 35.00 | 0.4 | 8125 | 2550 | 12660 | 2640×2820×2810 | |||||
| 8000 | 6.520 | 40.50 | 0.0 | 9620 | 2780 | 15100 | 2710×2840×3040 | 1475/1475 | ||||
| 10000 | 7.700 | 47.70 | 0.6 | 11660 | 3070 | 17480 | 2850×2880×3265 | |||||
This transformer reduces no-load loss by approximately 12%, significantly lowering electricity costs and improving long-term economic and environmental efficiency.
Yes, it features excellent moisture-proof capabilities and can operate in 100% humidity environments. It does not require preheating before operation or dehumidification during intermittent use.
The maximum environmental temperature is 40 ℃. The minimum operating temperature is -25 ℃ for outdoor dry-type installations and -5 ℃ for indoor installations.
Yes. Due to its strong heat dissipation capabilities, it can achieve up to 150% rated load operation under cold air conditions to handle short-term load peaks.
The installation altitude should not exceed 1000 meters. The power supply voltage waveform must approximate a sine wave, and the three-phase supply should be roughly symmetrical.