FKRN12 - 12D Indoor High-Voltage Puffer-Type Load Break Switch / Fuse Combination Apparatus
Overview
The FKN12-12 / FKRN12-12D series indoor high-voltage air load break switches/fuse combination electrical apparatus are suitable for three-phase high-voltage switching devices of 12kV and below. They are primarily used for the control and protection of transformers, cables, overhead lines, and other power equipment. These devices are especially suitable for urban and rural power distribution networks, terminal substations, and box-type substations. They are also applicable to ring main units and dual power supply systems for unit control and protection.
Production Features
Compact Structure, Small Footprint
Modular design allows easy integration into switchgear panels, saving installation space.
Puffer-Type Arc Extinguishing Technology
Utilizes compressed air arc extinguishing for strong breaking capacity and effective arc suppression.
Integrated Multi-Functionality
Combines load break switch and fuse, providing disconnection, load breaking, and protection in one unit.
Fast Fault Interruption
High-speed fuse clearing ensures quick isolation of fault currents, minimizing equipment damage.
Visible Isolation Gap
Provides a clearly visible disconnection point to ensure maintenance safety and meet interlocking requirements.
Flexible Operation Options
Supports both manual and motorized operation, suitable for local or remote control.
Long Mechanical Life, Low Maintenance
Designed for over 2000 operations with a robust mechanism and reduced service requirements.
Wide Application Adaptability
Suitable for urban and rural power networks, compact substations, and ring main units (RMUs).
Standards Compliance & High Reliability
Compliant with GB3804, GB16926 and other relevant standards, ensuring high interchangeability and reliability.
Product Parameter
|
No. |
Item |
Unit |
FKN12-12D |
FKRN12-12D |
|
1 |
Rated Voltage |
kV |
12 |
12 |
|
2 |
Rated Frequency |
Hz |
50 |
50 |
|
3 |
Rated Current |
A |
630 |
125 |
|
4 |
Lightning Impulse Withstand Voltage |
kV |
Phase to earth 42, across isolating gap 48 |
Phase to earth 42, across isolating gap 48 |
|
5 |
1min Power Frequency Withstand Voltage |
kV |
Phase to earth 75, across isolating gap 85 |
Phase to earth 75, across isolating gap 85 |
|
6 |
Rated Short-Time Withstand Current |
kA |
Load break switch: 20; Earthing switch: 20 |
|
|
7 |
Rated Short-Time Withstand Duration |
s |
Load break switch: 4; Earthing switch: 2 |
|
|
8 |
Rated Peak Withstand Current (Peak) |
kA |
50 |
|
|
9 |
Rated Breaking Current |
A |
Load break switch: 630; Close-open breaking current: 630; |
|
|
10 |
Rated Transformer Breaking Capacity |
kVA |
1250 |
|
|
11 |
Rated Short-Circuit Breaking Current (Fuse-linked) |
kA |
|
31.5 |
|
12 |
Rated Transfer Current |
A |
1200 |
|
|
13 |
Mechanical Life |
times |
2000 |
|
|
14 |
Operating Sequence |
|
0-0.3s-CO-180s-CO |
|
|
15 |
Closing Time |
ms |
≤65 |
|
|
16 |
Opening Time |
ms |
≤10 |
|