Leave Your Message
Products Categories
Featured Products

GN19-12 Indoor High Voltage Isolation Switch

GN19-12 series indoor high-voltage isolation relationship high-voltage switchgear is used in power systems with rated voltage of 12KV, AC 50Hz and below. It is equipped with CS6-1 manual operating mechanism and is used for opening and closing circuits under voltage and no load. It also has derivative products such as anti fouling type, high-altitude type, and equipped with live display devices.

    Overview

    GN19-12 series indoor high-voltage isolation relationship high-voltage switchgear is used in power systems with rated voltage of 12KV, AC 50Hz and below. It is equipped with CS6-1 manual operating mechanism and is used for opening and closing circuits under voltage and no load. It also has derivative products such as anti fouling type, high-altitude type, and equipped with live display devices.

    The isolation switch in this department is equipped with the CS6-1 manual operating mechanism.

    This series of isolating switches is a three pole type, consisting of a chassis, a shaft, a lever, a porcelain pillar insulator, a switch blade, and a terminal block. The rotating shaft is mounted on the chassis and has three pairs of levers welded on it. The levers are connected to a ceramic insulator and a knife chain through a pull rod. The rotating shaft extends out of the chassis, and any section of it can be connected to the operating mechanism.

    Type C is a through wall type. Where C1 represents rotation on the through wall side; C2 represents the disconnection on the through wall side;C3 indicates that both sides are on the through wall side.

    Model and meaning

     1.GN19-12 Indoor High Voltage Isolation Switch.jpg

    Environmental condition of use

    Altitude not exceeding 1000m;

    Surrounding air temperature: -25 ℃~+40 ℃;

    The seismic intensity shall not exceed 8 degrees;

    Relative humidity of the surrounding environment: daily average not exceeding 95%, monthly average not exceeding 90%;

    Installation location: No fire, flammable, explosive, severely polluted, chemically corroded, or violently vibrating areas.

    Technical parameter

    Item

    Unit

    Parameter

    Rated Voltage

    KV

    12

    1min Power Frequency Withstand Voltage

    To ground

    KV

    42

    Break

    KV

    48

    Lightning Impulse Withstand Voltage (Peak Value)

    To Ground

    KV

    75

    Break

    KV

    85

    Rated Frequency

    HZ

    50

    Rated Current

    A

    400

    630

    1000 1250

    Rated Short - time Withstand Current

    KA

    16

    20

    16

    20

    25

    20

    25

    31.5

    Rated Peak Withstand Current

    KA

    40

    50

    40

    50

    63

    50

    63

    80

    Duration of Rated Short - time Withstand Current Main Switch/Earthing Switch

    s

    4/2

    Creepage Distance

    mm

    300 - 380

    Mechanical Life

    Times

    2000

    Appearance and installation size

    未标题-2.jpg

    Product type

    Product type A B C D E F
    GN19-12/400 450 436 4-14x24 210 230 250 620 660 700 870 900 940
    GN19-12/630 490 436
    510 530 4-18x28
    GN19-12C/400 420 625 4-14x24
    GN19-12C/630 460 625
    505 745 4-18x28