Indoor High-Voltage Earthing Switch JN15-12/31.5-80 - Reliable China Suppliers & Factory Solutions
- Altitude: Not exceeding 1000m;
- Ambient air temperature: Upper limit 40°C, lower limit - 25°C;
- Seismic intensity: Not exceeding 8 degrees;
- No places with flammable, explosive, heavy dust, chemical corrosion, and severe vibration;
- Ambient air should be free from obvious pollution by corrosive or flammable gases, water vapor, etc.;
- No frequent severe vibration.
| No. | Item | Unit | Data |
|---|---|---|---|
| 1 | Rated Current | kA | 12 |
| 2 | Rated Short - Time Withstand Current | kA | 31.5 |
| 3 | Rated Short - Circuit Duration | s | 4 |
| 4 | Rated Short - Circuit Making Current | kA | 80 |
| 5 | Rated Peak Withstand Current | kA | 80 |
| 6 | Phase - to - Phase Center Distance | mm | 210, 230, 250, 275 |
| 7 | Rated Insulation Level | - | - |
| 1min Power Frequency Withstand Voltage | kV | 42 | |
| Lightning Impulse Voltage | kV | 75 |
| Model Specification | L | E | C |
|---|---|---|---|
| JN15 - 12/31.5 - 210 | 655 | 210 | 516 |
| JN15 - 12/31.5 - 230 | 710 | 230 | 556 |
| JN15 - 12/31.5 - 250 | 760 | 250 | 596 |
| JN15 - 12/31.5 - 275 | 810 | 275 | 646 |
It meets the domestic GB1985-2004 standard for High-Voltage AC Disconnectors and Earthing Switches as well as the international IEC62271 standard.
It is designed for indoor AC power systems operating at a frequency of 50Hz and a voltage rating below 12kV.
The rated short-time withstand current is 31.5 kA with a rated short-circuit duration of 4 seconds.
The switch should be operated at altitudes not exceeding 1000 meters, with ambient air temperatures ranging from a lower limit of -25°C to an upper limit of 40°C.
Yes, the JN15-12/31.5-80 earthing switch is compatible and can be used in combination with live-line display devices.
The available phase-to-phase center distances are 210 mm, 230 mm, 250 mm, and 275 mm depending on the model specification.