Indoor High Voltage VS1 Vacuum Circuit Breaker

The ZN63(VS1)-12 series indoor withdrawable high-voltage vacuum circuit breakers are three-phase AC 50Hz, indoor switchgear with a rated voltage of 12kV. They are used for the control and protection of industrial and mining enterprises, power plants, substations, and electrical facilities, and are suitable for frequently operated sites.

    Overview

    The operating mechanism and the circuit breaker body are integrated. The design can be used as a fixed installation unit, or can be equipped with a dedicated propulsion mechanism to form a withdrawable unit. The main circuit part can adopt an integrally encapsulated pole to achieve miniaturization, high reliability, and maintenance-free of the circuit breaker. It can be matched with KYN28A - 12(GZS) and other mid-mounted withdrawable switchgear cabinets. The fixed type can also be matched with XGN series fixed switchgear cabinets.

    Operating Environment

    Ambient Temperature: Not higher than 40°C, and not lower than -10°C (Transportation and storage at -30°C is allowed).

    Altitude: Not exceeding 1000m. (If a higher altitude is required, the rated insulation level shall be increased accordingly.)

    Relative Humidity: The daily average value shall not be greater than 95%, the daily average value of saturated vapor pressure shall not be greater than 2.2×10⁻³MPa, and the monthly average value shall not be greater than 1.8×10⁻³MPa.

    Seismic Intensity: Not exceeding 8 degrees.

    Location: No fire, explosion, severe pollution, chemical corrosion, or violent vibration.

    Product Parameters

    Item

    Description

    Unit

    Data

    1

    Rated voltage

    kV

    24

    2

    Max. voltage

    kV

    24

    3

    Rated current

    A

    630/1250/2500

    4

    Rated short circuit breaking current

    kA

    20/25/31.5

    5

    Rated short circuit making current

    kA

    50/63/80

    6

    Rated peak withstand current

    kA

    50/63/80

    7

    4S Rated withstand current

    kA

    20/25/31.5

    8

    Rated insulation level - Power frequency voltage(when losing a circuit)

    kV

    Dreaker 85

    8

    Rated insulation level - Impulse withstand voltage(when losing a circuit)

    kV

    Dreaker 125

    9

    Rated operating sequence

    -

    OC - 0.3s - CO - 180S - CO

    10

    Mechanical life

    Times

    20000

    11

    Rated short circuit current breaking time

    Times

    274

    12

    Rated close brake voltage of operating machine

    V

    110,220

    13

    Rated break brake voltage of operating machine

    V

    110,220

    14

    Contact stroke

    mm

    13±1

    15

    Exceed range(the compress length of contact spring)

    mm

    3.5±0.5

    16

    Different period of three - phase break and close break

    ms

    ≤2

    17

    The jump time of contact close break

    ms

    ≤2

    18

    Average break speed

    m/s

    1.1 - 1.7

    19

    Average closing speed

    m/s

    0.6 - 1.1

    20

    Opening time - Under max. operating voltage

    S

    ≤0.05

    20

    Opening time - Under min. operating voltage

    S

    ≤0.08

    21

    Closing time

    s

    0.1

    22

    Resistance of each phase main loop

    μΩ

    830≤50;1250≤45;1600 - 2500≤40

    23

    Contacts limit erosion

    mm

    3