Intelligent Universal Air Circuit Breaker (ACB) 400A-6300A - Reliable China Suppliers & Factory for Low-Voltage Solutions
Overview
W1 air circuit breaker is a universal low-voltage circuit breaker, suitable for distribution networks with AC 50Hz, rated voltage up to 660V (690V) and below, and rated current of 400A ~ 6300A. Its main function is to distribute electric energy and protect lines and power equipment from overload, undervoltage, short circuit, single-phase grounding and other fault hazards. It is widely used in power distribution of industrial and mining enterprises, low-voltage side of power plants and substations, and power distribution systems of commercial buildings.
Core Technical Features
Protection Functions
- Intelligent Release: Enables long-time delayed inverse-time overload protection.
- Short-Circuit Protection: Short-time delayed inverse-time/timed and instantaneous protection.
- Ground Protection: Single-phase ground protection to prevent electrical hazards.
Structural Design
- Contact System: Multi-contact parallel structure + insulated small chamber + arc-extinguishing system (breaking capacity 80-100kA).
- Operating Mechanism: Spring-energy-storage supporting electric/manual energy storage.
- Types: Draw-out type (three-position interchangeable) and fixed type (simple, cost-effective).
Intelligent Control
- Releases: Classified into electronic, standard, and communication types.
- Four-Remote Docking: Remote measurement, remote signal, remote control, and remote adjustment.
- Options: Voltage display, load monitoring, disconnection diagnosis, and harmonic monitoring.
Product Parameters
| Parameter Category | Parameter | Technical Specifications | Explanation/Basis |
|---|---|---|---|
| Basic Electrical Parameters | Rated Working Voltage (Ue) | AC 400V, 690V (common), up to 1000V | Suitable for low-voltage distribution systems |
| Rated Current (In) | 400A, 630A, 800A, 1000A, 1250A, 1600A, 2000A, 2500A, 3200A, 4000A, 5000A, 6300A | Covers different power distribution capacities | |
| Rated Short-Circuit Breaking Capacity (Icu) | 35kA, 50kA, 65kA, 80kA, 100kA (RMS) | Indicates fault interruption capability | |
| Rated Service Short-Circuit Breaking Capacity (Ics) | Typically 50%, 75%, or 100% of Icu (e.g., Ics = Icu) | Reflects repeated fault interruption capability | |
| Rated Short-Time Withstand Current (Icw) | 20kA, 30kA, 40kA (withstand for 4s) | Thermal withstand capability for short circuits | |
| Protection Function Parameters | Overload Long-Time Delay Protection (Ir1) | (0.4–1)In continuously adjustable, inverse-time characteristic | Follows IEC 60947-2 standard curves |
| Short-Circuit Short-Time Delay Protection (Ir2) | (2–10)In continuously adjustable, timed/inverse-time selectable | Enables selective tripping with upstream/downstream protection | |
| Short-Circuit Instantaneous Protection (Im) | (5–20)In continuously adjustable (fixed multiples in some models) | Rapid interruption of severe short circuits | |
| Single-Phase Ground Fault Protection | Ground fault current threshold (e.g., 0.2In–1In adjustable) | Requires zero-sequence current transformer | |
| Mechanical & Structural Parameters | Operating Mechanism Type | Spring energy-storage mechanism (electric/manual energy storage) | Electric for automation, manual for debugging |
| Mounting Type | Draw-out type, fixed type | Draw-out type supports three positions (connect/test/disconnect) | |
| Pole Number | 3P, 4P | Suitable for 3-phase 3-wire/4-wire systems | |
| Arcing Distance | 0mm (zero arcing design) | Enables compact installation without arc spraying | |
| Environmental & Adaptation Parameters | Ambient Temperature | -5°C–+40°C (24h average ≤35°C); extended to -40°C–+70°C for some derivatives | Complies with GB 14048.2 standard |
| Altitude | ≤2000m (insulation level must be upgraded for higher altitudes) | Special design required for high altitudes | |
| Protection Level | IP30 (IP40/IP54 optional after cabinet installation) | Dust and foreign object protection | |
| Intelligent Control Parameters | Release Type | Electronic type, intelligent type (M/H/L models) | Intelligent models support communication and parameter display |
| Communication Interface | RS485 (supports Modbus, Profibus, etc.) | Enables "Four Remotes" (remote measurement/signal/control/adjustment) | |
| Other Parameters | Mechanical Life | 20,000–30,000 operations (closing/opening) | Impacts long-term reliability |
| Control Power Supply Voltage | AC220V, DC220V, AC380V, etc. | Must match system control power supply |
Frequently Asked Questions
The W1 air circuit breaker accommodates a wide range of distribution capacities with rated currents starting from 400A up to 6300A (including 400A, 630A, 800A, 1000A, 1250A, 1600A, 2000A, 2500A, 3200A, 4000A, 5000A, and 6300A).
The intelligent release provides comprehensive protection, including long-time delayed inverse-time overload protection, short-time delayed inverse-time/timed short-circuit protection, instantaneous short-circuit protection, and single-phase ground protection.
The draw-out type features a three-position design (connect, test, disconnect) with high interchangeability for identical current ratings. The fixed type offers a simpler structure and lower overall cost.
Yes. The communication-type intelligent release supports "four-remote" capabilities (remote measurement, remote signal, remote control, remote adjustment) through an RS485 interface supporting Modbus, Profibus, and other protocols.
The W1 circuit breaker achieves a high breaking capacity of 80–100kA due to its multi-contact parallel structure and arc-extinguishing system. It also features a zero-arcing design (0mm arcing distance) for compact cabinet installations.
The standard ambient operating temperature is -5°C to +40°C (with derivatives extending from -40°C to +70°C). It is suitable for installations at altitudes up to 2000 meters.