Intelligent Universal Air Circuit Breaker (ACB) - China Suppliers and Factory for Low-Voltage Power Distribution
Overview
W1 air circuit breaker is a universal low-voltage circuit breaker, suitable for distribution networks with AC 50Hz, rated voltage up to 660V (690V) and below, and rated current of 400A ~ 6300A. Its main function is to distribute electric energy and protect lines and power equipment from overload, undervoltage, short circuit, single-phase grounding and other fault hazards. It is widely used in power distribution of industrial and mining enterprises, low-voltage side of power plants and substations, and power distribution systems of commercial buildings.
Core Technical Features
(I) Protection Functions
The intelligent release enables long-time delayed inverse-time overload protection, short-time delayed inverse-time/timed short-circuit protection, instantaneous short-circuit protection, and single-phase ground protection. It accurately responds to different faults, quickly breaks the circuit, minimizes the power outage range, and prevents electrical hazards.
(II) Structural Design
Contact System: Adopts a multi-contact parallel structure + insulated small chamber + arc-extinguishing system, improving breaking speed and capacity, achieving a high breaking capacity (80 - 100kA).
Operating Mechanism: Spring-energy-storage mechanism, supporting electric/manual energy storage, closing and opening. Fast closing suppresses inrush current. Available in draw-out type and fixed type.
(III) Intelligent Control & Expansion
Intelligent releases are classified into electronic, standard, and communication types. The communication type supports "four-remote" (remote measurement, remote signal, remote control, remote adjustment) docking with intelligent systems. Optional functions include voltage display, load monitoring, disconnection diagnosis, and harmonic monitoring.
Product Parameters
| Parameter Category | Parameter | Technical Specifications | Explanation/Basis |
|---|---|---|---|
| Basic Electrical Parameters | Rated Working Voltage (Ue) | AC 400V, 690V (common), up to 1000V | Suitable for low-voltage distribution systems |
| Rated Current (In) | 400A, 630A, 800A, 1000A, 1250A, 1600A, 2000A, 2500A, 3200A, 4000A, 5000A, 6300A | Covers different power distribution capacities | |
| Rated Short-Circuit Breaking Capacity (Icu) | 35kA, 50kA, 65kA, 80kA, 100kA (RMS) | Indicates fault interruption capability | |
| Rated Service Short-Circuit Breaking Capacity (Ics) | Typically 50%, 75%, or 100% of Icu (e.g., Ics = Icu) | Reflects repeated fault interruption capability | |
| Rated Short-Time Withstand Current (Icw) | 20kA, 30kA, 40kA (withstand for 4s) | Thermal withstand capability for short circuits | |
| Protection Function Parameters | Overload Long-Time Delay Protection (Ir1) | (0.4–1)In continuously adjustable, inverse-time characteristic | Follows IEC 60947-2 standard curves |
| Short-Circuit Short-Time Delay Protection (Ir2) | (2–10)In continuously adjustable, timed/inverse-time selectable | Enables selective tripping with upstream/downstream protection | |
| Short-Circuit Instantaneous Protection (Im) | (5–20)In continuously adjustable (fixed multiples in some models) | Rapid interruption of severe short circuits | |
| Single-Phase Ground Fault Protection | Ground fault current threshold (e.g., 0.2In–1In adjustable) | Requires zero-sequence current transformer | |
| Mechanical & Structural Parameters | Operating Mechanism Type | Spring energy-storage mechanism (electric/manual energy storage) | Electric for automation, manual for debugging |
| Mounting Type | Draw-out type, fixed type | Draw-out type supports three positions (connect/test/disconnect) | |
| Pole Number | 3P, 4P | Suitable for 3-phase 3-wire/4-wire systems | |
| Arcing Distance | 0mm (zero arcing design) | Enables compact installation without arc spraying | |
| Environmental & Adaptation Parameters | Ambient Temperature | -5°C–+40°C (24h average ≤35°C); extended to -40°C–+70°C for some derivatives | Complies with GB 14048.2 standard |
| Altitude | ≤2000m (insulation level must be upgraded for higher altitudes) | Special design required for high altitudes | |
| Protection Level | IP30 (IP40/IP54 optional after cabinet installation) | Dust and foreign object protection | |
| Intelligent Control Parameters | Release Type | Electronic type, intelligent type (M/H/L models) | Intelligent models support communication and parameter display |
| Communication Interface | RS485 (supports Modbus, Profibus, etc.) | Enables "Four Remotes" (remote measurement/signal/control/adjustment) | |
| Other Parameters | Mechanical Life | 20,000–30,000 operations (closing/opening) | Impacts long-term reliability |
| Control Power Supply Voltage | AC220V, DC220V, AC380V, etc. | Must match system control power supply |
Frequently Asked Questions (FAQ)
A1: The W1 air circuit breaker is used in distribution networks with AC 50Hz, rated voltages up to 660V/690V, and rated currents from 400A to 6300A. It distributes electrical energy and protects lines and power equipment against overload, undervoltage, short circuits, and single-phase grounding faults.
A2: The intelligent release provides long-time delayed inverse-time overload protection, short-time delayed inverse-time/timed short-circuit protection, instantaneous short-circuit protection, and single-phase ground fault protection to minimize power outage ranges.
A3: The draw-out type supports three interchangeable positions (connect, test, and disconnect) for easy maintenance and replacement. The fixed type offers a simpler structure and is a more cost-effective option.
A4: Yes, the communication-type intelligent release supports "four-remote" functions (remote measurement, remote signal, remote control, and remote adjustment) via an RS485 interface supporting Modbus, Profibus, and other protocols.
A5: Depending on the specifications, the W1 circuit breaker features a high breaking capacity ranging from 35kA up to 100kA (RMS).
A6: The standard operating temperature ranges from -5°C to +40°C. However, specialized derivatives can extend the operating limits from -40°C up to +70°C to meet harsh environmental demands.