Intelligent Universal Air Circuit Breaker (ACB)
Overview
W1 air circuit breaker is a universal low-voltage circuit breaker, suitable for distribution networks with AC 50Hz, rated voltage up to 660V (690V) and below, and rated current of 400A ~ 6300A. Its main function is to distribute electric energy and protect lines and power equipment from overload, undervoltage, short circuit, single-phase grounding and other fault hazards. It is widely used in power distribution of industrial and mining enterprises, low-voltage side of power plants and substations, and power distribution systems of commercial buildings.
Core Technical Features
(I) Protection Functions
The intelligent release enables long - time delayed inverse - time over - load protection,short - time delayed inverse - time/timed short - circuit protection, instantaneous short - circuit protection, and single - phase ground protection. It accurately responds to different faults, quickly breaks the circuit, minimizes the power outage range, and prevents electrical hazards.
(II) Structural Design
Contact System: Adopts a multi - contact parallel structure + insulated small chamber + arc - extinguishing system, improving breaking speed and capacity, achieving a high breaking capacity (80 - 100kA).
Operating Mechanism: Spring - energy - storage mechanism, supporting electric/manual energy storage, closing and opening. Fast closing suppresses inrush current during closing. Available in draw - out type (three - position interchangeable, with interchangeability for the same current) and fixed type (simple structure, low cost).
(III) Intelligent Control and Expansion
Intelligent releases are classified into electronic, standard, and communication types. The communication type supports "four - remote" (remote measurement, remote signal, remote control, remote adjustment) docking with intelligent systems. Optional functions include voltage display, load monitoring, disconnection diagnosis, and harmonic monitoring, meeting the needs of refined management.
Product Parameters
| Parameter Category | Parameter | Technical Specifications | Explanation/Basis |
| Basic Electrical Parameters | Rated Working Voltage (Ue) | AC 400V, 690V (common), up to 1000V | Suitable for low-voltage distribution systems |
| Rated Current (In) | 400A, 630A, 800A, 1000A, 1250A, 1600A, 2000A, 2500A, 3200A, 4000A, 5000A, 6300A | Covers different power distribution capacities | |
| Rated Short-Circuit Breaking Capacity (Icu) | 35kA, 50kA, 65kA, 80kA, 100kA (RMS) | Indicates fault interruption capability | |
| Rated Service Short-Circuit Breaking Capacity (Ics) | Typically 50%, 75%, or 100% of Icu (e.g., Ics = Icu) | Reflects repeated fault interruption capability | |
| Rated Short-Time Withstand Current (Icw) | 20kA, 30kA, 40kA (withstand for 4s) | Thermal withstand capability for short circuits | |
| Protection Function Parameters | Overload Long-Time Delay Protection (Ir1) | (0.4–1)In continuously adjustable, inverse-time characteristic | Follows IEC 60947-2 standard curves |
| Short-Circuit Short-Time Delay Protection (Ir2) | (2–10)In continuously adjustable, timed/inverse-time selectable | Enables selective tripping with upstream/downstream protection | |
| Short-Circuit Instantaneous Protection (Im) | (5–20)In continuously adjustable (fixed multiples in some models) | Rapid interruption of severe short circuits | |
| Single-Phase Ground Fault Protection | Ground fault current threshold (e.g., 0.2In–1In adjustable) | Requires zero-sequence current transformer | |
| Mechanical & Structural Parameters | Operating Mechanism Type | Spring energy-storage mechanism (electric/manual energy storage) | Electric for automation, manual for debugging |
| Mounting Type | Draw-out type, fixed type | Draw-out type supports three positions (connect/test/disconnect) | |
| Pole Number | 3P, 4P | Suitable for 3-phase 3-wire/4-wire systems | |
| Arcing Distance | 0mm (zero arcing design) | Enables compact installation without arc spraying | |
| Environmental & Adaptation Parameters | Ambient Temperature | -5°C–+40°C (24h average ≤35°C); extended to -40°C–+70°C for some derivatives | Complies with GB 14048.2 standard |
| Altitude | ≤2000m (insulation level must be upgraded for higher altitudes) | Special design required for high altitudes | |
| Protection Level | IP30 (IP40/IP54 optional after cabinet installation) | Dust and foreign object protection | |
| Intelligent Control Parameters | Release Type | Electronic type, intelligent type (M/H/L models) | Intelligent models support communication and parameter display |
| Communication Interface | RS485 (supports Modbus, Profibus, etc.) | Enables "Four Remotes" (remote measurement/signal/control/adjustment) | |
| Other Parameters | Mechanical Life | 20,000–30,000 operations (closing/opening) | Impacts long-term reliability |
| Control Power Supply Voltage | AC220V, DC220V, AC380V, etc. | Must match system control power supply |