Leave Your Message
Products Categories
Featured Products

Intelligent Universal Air Circuit Breaker (ACB)

W1 air circuit breaker is a universal low-voltage circuit breaker, suitable for distribution networks with AC 50Hz, rated voltage up to 660V (690V) and below, and rated current of 400A ~ 6300A. Its main function is to distribute electric energy and protect lines and power equipment from overload, undervoltage, short circuit, single-phase grounding and other fault hazards. It is widely used in power distribution of industrial and mining enterprises, low-voltage side of power plants and substations, and power distribution systems of commercial buildings.

    Overview

    W1 air circuit breaker is a universal low-voltage circuit breaker, suitable for distribution networks with AC 50Hz, rated voltage up to 660V (690V) and below, and rated current of 400A ~ 6300A. Its main function is to distribute electric energy and protect lines and power equipment from overload, undervoltage, short circuit, single-phase grounding and other fault hazards. It is widely used in power distribution of industrial and mining enterprises, low-voltage side of power plants and substations, and power distribution systems of commercial buildings.

    Core Technical Features

    (I) Protection Functions

    The intelligent release enables long - time delayed inverse - time over - load protection,short - time delayed inverse - time/timed short - circuit protection, instantaneous short - circuit protection, and single - phase ground protection. It accurately responds to different faults, quickly breaks the circuit, minimizes the power outage range, and prevents electrical hazards.

    (II) Structural Design

    Contact System: Adopts a multi - contact parallel structure + insulated small chamber + arc - extinguishing system, improving breaking speed and capacity, achieving a high breaking capacity (80 - 100kA).

    Operating Mechanism: Spring - energy - storage mechanism, supporting electric/manual energy storage, closing and opening. Fast closing suppresses inrush current during closing. Available in draw - out type (three - position interchangeable, with interchangeability for the same current) and fixed type (simple structure, low cost).

    (III) Intelligent Control and Expansion

    Intelligent releases are classified into electronic, standard, and communication types. The communication type supports "four - remote" (remote measurement, remote signal, remote control, remote adjustment) docking with intelligent systems. Optional functions include voltage display, load monitoring, disconnection diagnosis, and harmonic monitoring, meeting the needs of refined management.

    Product Parameters

    Parameter Category Parameter Technical Specifications Explanation/Basis
    Basic Electrical Parameters Rated Working Voltage (Ue) AC 400V, 690V (common), up to 1000V Suitable for low-voltage distribution systems
    Rated Current (In) 400A, 630A, 800A, 1000A, 1250A, 1600A, 2000A, 2500A, 3200A, 4000A, 5000A, 6300A Covers different power distribution capacities
    Rated Short-Circuit Breaking Capacity (Icu) 35kA, 50kA, 65kA, 80kA, 100kA (RMS) Indicates fault interruption capability
    Rated Service Short-Circuit Breaking Capacity (Ics) Typically 50%, 75%, or 100% of Icu (e.g., Ics = Icu) Reflects repeated fault interruption capability
    Rated Short-Time Withstand Current (Icw) 20kA, 30kA, 40kA (withstand for 4s) Thermal withstand capability for short circuits
    Protection Function Parameters Overload Long-Time Delay Protection (Ir1) (0.4–1)In continuously adjustable, inverse-time characteristic Follows IEC 60947-2 standard curves
    Short-Circuit Short-Time Delay Protection (Ir2) (2–10)In continuously adjustable, timed/inverse-time selectable Enables selective tripping with upstream/downstream protection
    Short-Circuit Instantaneous Protection (Im) (5–20)In continuously adjustable (fixed multiples in some models) Rapid interruption of severe short circuits
    Single-Phase Ground Fault Protection Ground fault current threshold (e.g., 0.2In–1In adjustable) Requires zero-sequence current transformer
    Mechanical & Structural Parameters Operating Mechanism Type Spring energy-storage mechanism (electric/manual energy storage) Electric for automation, manual for debugging
    Mounting Type Draw-out type, fixed type Draw-out type supports three positions (connect/test/disconnect)
    Pole Number 3P, 4P Suitable for 3-phase 3-wire/4-wire systems
    Arcing Distance 0mm (zero arcing design) Enables compact installation without arc spraying
    Environmental & Adaptation Parameters Ambient Temperature -5°C–+40°C (24h average ≤35°C); extended to -40°C–+70°C for some derivatives Complies with GB 14048.2 standard
    Altitude ≤2000m (insulation level must be upgraded for higher altitudes) Special design required for high altitudes
    Protection Level IP30 (IP40/IP54 optional after cabinet installation) Dust and foreign object protection
    Intelligent Control Parameters Release Type Electronic type, intelligent type (M/H/L models) Intelligent models support communication and parameter display
    Communication Interface RS485 (supports Modbus, Profibus, etc.) Enables "Four Remotes" (remote measurement/signal/control/adjustment)
    Other Parameters Mechanical Life 20,000–30,000 operations (closing/opening) Impacts long-term reliability
    Control Power Supply Voltage AC220V, DC220V, AC380V, etc. Must match system control power supply