KYN61-40.5 Metalclad & Withdrawable AC Switchgear
Overview
The KYN61-40.5 Metalclad & Withdrawable AC Switchgear (hereinafter referred to as switchgear) is a three - phase AC 50Hz, rated voltage 40.5kV indoor complete power distribution device. It is used in power plants, substations, and industrial and mining enterprises for receiving and distributing electrical energy, and plays a role in controlling, protecting, and detecting circuits. It can also be used in places with frequent operations. This switchgear complies with standards such as GB/T11022 - 1999, GB3906 - 2006, and DL404 - 1997.
Structural Features
The cabinet structure adopts an assembled type, and the circuit breaker adopts a handcart floor - type structure.
It is equipped with a new - type composite insulation vacuum circuit breaker, which has the characteristics of good interchangeability and simple replacement.
The handcart frame is equipped with a lead - screw nut advancing mechanism, which can easily move the handcart and prevent damage to the advancing structure due to misoperation.
All operations can be carried out with the cabinet door closed.
The interlocks among the main switch, handcart, and switchgear door all adopt a mandatory mechanical interlocking method to meet the "five - prevention" functions.
The cable room has sufficient space and can connect multiple cables.
The quick - earthing switch is used for earthing and loop short - circuit.
The protection level of the enclosure is IP3X, and when the handcart room door is open, the protection level is IP2X.
The product complies with GB3906 - 1991, DL404 - 1997, and refers to the international IEC - 298 standard.3.Schematic.
Model Meaning

Service Environment Conditions
Upper limit of ambient temperature: +40°C, and the average value measured within 24 hours shall not exceed 35°C; lower limit: -15°C.
Altitude: Not exceeding 1000 meters.
Relative humidity: Daily average value not exceeding 95%, monthly average value not exceeding 90%.
Earthquake intensity: Not exceeding magnitude 8.
Water vapor pressure: Daily average value not exceeding 2.2kPa, monthly average value not exceeding 90%.
Technical Parameters
Main Technical Parameters of Vacuum Switchgear

Main Technical Parameters of Vacuum Circuit Breaker