LSY-10/110 Current Transformer - Reliable Medium-Voltage Solution from China Suppliers and Factory

The LSY-10 current transformer represents a cutting-edge solution for measurement and protection in medium-voltage power systems. This three-phase integrated current transformer is specifically engineered for AC power systems operating at 10kV and below. As one of the leading products from China, it excels in accurately measuring three-phase current and zero-sequence current. The LSY-10 is extensively utilized in various current monitoring applications, including ring main unit switchgear, pole-mounted switches, and multiple cable circuits. Trusted by numerous suppliers, this product showcases the high-quality manufacturing standards of our factory, making it an ideal choice for your power system needs.

    Overview

    The LSY-10 current transformer is a three-phase integrated combined current transformer, specifically designed for measurement and protection tasks in medium-voltage power systems. It is suitable for AC power systems of 10kV and below, capable of accurately measuring three-phase current and zero-sequence current, and is widely used in current monitoring scenarios such as ring main unit switchgear, pole-mounted switches, and multiple cable circuits.

    This transformer is uniquely designed. Its core and secondary winding are vacuum-cast with high-quality epoxy resin and sealed in a flame-retardant plastic housing. This design not only effectively prevents the equipment from being eroded by a humid environment but also ensures the long-term stability of product performance with almost no maintenance required, greatly reducing operating costs. In practical applications, the LSY-10 can convert the large current on the primary side into a small current on the secondary side in proportion, facilitating the access of measuring instruments and protection devices, and providing reliable data support for the safe and stable operation of the power system.

    Product Advantages

    The LSY-10 current transformer has many significant advantages:

    High-Precision Measurement

    Provides accurate data for the metering and monitoring of the power system, helping to improve the operating efficiency of the power system.

    High Reliability & Craftsmanship

    Stems from its excellent materials and exquisite craftsmanship, enabling it to work stably in harsh environments and reducing the probability of failures.

    Convenient Installation

    Compact structural design makes installation in various switchgear and cable lines simple and efficient.

    In summary, the LSY-10 current transformer, with its excellent performance, reliable quality, and convenient installation method, has become an ideal choice for current measurement and protection in medium-voltage power systems, escorting the stable operation of modern power networks.

    Technical Parameters of LSY-10 Current Transformer

    Item Parameter
    Rated Frequency 50Hz or 60Hz
    Rated Secondary Current 5A or 1A
    Rated Short-time Thermal Current 40kA, 1s
    Rated Continuous Thermal Current 120%In
    Load Power Factor COSφ = 0.8 (lagging)
    Instrument Security Factor FS≤10
    Accuracy Limitation Factor (Protection) 10P10, 10P15, 10P20, etc.
    Ambient Temperature -25ºC to +40ºC
    Average Daily Temperature ≤40ºC
    Altitude ≤3000m
    Pollution Class III
    Power-frequency Withstand Voltage 3kV, 1min

    Frequently Asked Questions (FAQ)

    What is the primary application of the LSY-10 Current Transformer?
    The LSY-10 is engineered for measurement and protection in medium-voltage AC power systems (10kV and below). It is widely used in ring main unit (RMU) switchgear, pole-mounted switches, and multi-cable distribution circuits.
    Can the LSY-10 measure both three-phase current and zero-sequence current?
    Yes, the LSY-10 is a three-phase integrated combined current transformer capable of accurately capturing both three-phase operational currents and zero-sequence currents simultaneously for comprehensive monitoring and fault protection.
    How does the construction of the LSY-10 withstand harsh environmental conditions?
    Its core and secondary windings are vacuum-cast with premium epoxy resin and enclosed within a flame-retardant plastic housing, offering superior resistance to humidity, moisture erosion, and atmospheric degradation.
    What rated secondary currents are supported?
    The transformer supports standard rated secondary current outputs of either 5A or 1A, allowing seamless connectivity with standard metering instruments and protection relays.
    What are the environmental limits for operating the LSY-10?
    The unit operates reliably in ambient temperatures ranging from -25ºC to +40ºC (with a daily average temperature of ≤40ºC), at altitudes up to 3,000 meters, and under Pollution Class III conditions.
    Does the LSY-10 require regular maintenance?
    Due to its fully sealed epoxy-cast and flame-retardant structure, the unit delivers stable long-term performance and requires virtually zero maintenance, significantly lowering overall operational costs.