Leave Your Message

What are the significant characteristics of CKSG low-voltage three-phase reactor?

2025-08-25

1.Harmonic & Inrush Current Suppression

Suppresses harmonic currents (THDi ≤ 10% per GB/T 14549) and inrush currents during capacitor switching, preventing insulation breakdown of capacitors.

Mitigates switching overvoltages to maintain power factor stability (≥0.95) in low-voltage systems.

1.CKSG low voltage three-phase reactor.jpg

2.Power Quality Optimization

Absorbs dominant harmonics (5th, 7th, etc.) to reduce voltage total harmonic distortion (THDu ≤ 5%).

Stabilizes bus voltage fluctuations, ensuring compliance with GB/T 12325 for voltage quality.

2.CKSG low voltage three-phase reactor.jpg

3.Dry-Type Core Structure

Adopts laminated silicon steel core with low eddy current loss (≤0.3W/kg at 1.7T, 50Hz).

Vacuum Pressure Impregnation (VPI) process enhances insulation strength (dielectric withstand voltage ≥3kV) and moisture resistance (IP20 protection).

3.CKSG low voltage three-phase reactor.jpg

4.System Synergy with Capacitors

Forms LC filtering loops with BSMJ-series capacitors, reducing reactive power loss by 30-40%.

Supports stepwise compensation configurations (10-500kvar) for scalable reactive power control.

4.CKSG low voltage three-phase reactor.jpg

5.Reliability & Longevity

Temperature rise ≤65K under rated load, ensuring continuous operation at -25℃~+45℃.

Built-in thermal protection triggers alarm at core temperature >130℃ (Class B insulation).

5.CKSG low voltage three-phase reactor.jpg

6.Installation Flexibility

Vertical/horizontal mounting compatible with standard low-voltage switchgear (e.g., GGD, GCK cabinets).

Low noise design (≤55dB at 1m) suitable for indoor power distribution rooms.

7.Compliance with Standards

Meets JB/T 9644 (dry-type reactor technical specifications) and IEC 60289 for reactor performance.