What Is MCCB Breaking Capacity?

2026-08-29

How to Choose the Right Breaking Capacity for an MCCB?

1. What Is MCCB Breaking Capacity?

The breaking capacity of a Molded Case Circuit Breaker (MCCB) indicates the maximum prospective short-circuit current that the circuit breaker is designed to interrupt safely under specified conditions.

This is different from the rated current, which indicates the current the MCCB is designed to carry during normal operation. When a short circuit occurs, the fault current can rise far beyond the normal operating current. The MCCB must therefore have sufficient breaking capacity to interrupt the fault safely.

For low-voltage power distribution systems, breaking capacity is an important parameter when selecting an MCCB for electrical panels, industrial equipment, and distribution circuits.

塑壳断路器正面1.jpg

2. Why Is Breaking Capacity Important?

A short circuit can produce a very high current within a very short period. If the selected circuit breaker does not have sufficient interrupting capability, it may not be able to safely clear the fault.

Therefore, the breaking capacity of an MCCB should be considered together with the prospective short-circuit current at the installation point.

A simplified selection principle is:

Prospective Short-Circuit Current ≤ MCCB Breaking Capacity

For example, if the prospective short-circuit current of a distribution point is higher than the circuit breaker's specified breaking capacity, that MCCB would not be an appropriate choice for the application.

This is why selecting an MCCB based only on its rated current, such as 250A or 400A, is not sufficient.

3. Understanding Icu and Ics

Two important terms commonly found in MCCB technical specifications are Icu and Ics.

Parameter Meaning Selection Significance
lcu Ultimate short-circuit breaking capacity Indicates the maximum short-circuit current the breaker is designed to interrupt under specified test conditions
lcs Service short-circuit breaking capacity Indicates the short-circuit breaking capability associated with service-level performance
ln Rated current Indicates the normal current rating of the MCCB
ue Rated operational voltage Indicates the operating voltage for which the MCCB is specified

Icu and Ics should not be confused with the rated current of the MCCB.

For example, an MCCB may have a rated current of 400A, while its short-circuit breaking capacity may be specified as 50kA at a particular operating voltage. The two values describe completely different characteristics of the circuit breaker.

When comparing MCCBs, customers should therefore check the complete electrical specification rather than focusing on only one parameter.

4. How Does Voltage Affect Breaking Capacity?

Breaking capacity should always be evaluated together with the applicable operating voltage and the specific MCCB model.

The same product family may have different short-circuit ratings under different electrical conditions. Therefore, a breaking capacity value should not be considered independently from its corresponding voltage and test conditions.

When reviewing an MCCB datasheet, it is useful to check these parameters together:

Rated Operating Voltage → Rated Current → Icu → Ics

For example, the product data provided for this MCCB series lists different ultimate and service short-circuit breaking capacities across its models and current ratings.

Example of Product Parameters

MCCB Model Rated Current Ultimate Breaking Capacity Icu Service Breaking Capacity Ics
M1-63M 16–63A 50kA 35kA
M1-125L 16–125A 35kA 22kA
M1-125M 16–125A 50kA 35KA
M1-250L 100–250A 35kA 22kA
M1-250M 100–250A 50kA 35KA
M1-400L 225–400A 50kA 35KA
M1-630L 400–630A 50kA 35KA
M1-630M 400–630A 65kA 42KA
M1-800M 630–800A 75kA 50KA
M1-1250M 1000–1250A 100kA 65KA
M1-1600M 1600A 150kA 80KA

Note: The values above are based on the product parameter table provided for this MCCB series. The applicable breaking capacity should be confirmed against the specific model, rated voltage, and manufacturer's technical documentation before selection.

5. How to Choose the Right MCCB Breaking Capacity?

Selecting an appropriate MCCB can follow several basic steps.

Step 1: Confirm the System Voltage

Determine the rated operating voltage of the electrical system and make sure it is within the applicable rating of the MCCB.

Step 2: Determine the Normal Load Current

Calculate or obtain the expected operating current of the protected circuit and select an appropriate rated current.

Step 3: Determine the Prospective Short-Circuit Current

The prospective short-circuit current at the installation point is an important reference for selecting the required breaking capacity.

Step 4: Check Icu and Ics

Compare the required short-circuit protection level with the MCCB's specified Icu and Ics values.

Step 5: Confirm Other Requirements

The final selection should also consider the number of poles, protection characteristics, installation conditions, load type, and coordination with upstream and downstream protection devices.

6. FAQ

What is MCCB breaking capacity?

MCCB breaking capacity refers to the short-circuit current that the circuit breaker is designed to interrupt safely under specified conditions.

What is the difference between Icu and Ics?

Icu represents the ultimate short-circuit breaking capacity, while Ics represents the service short-circuit breaking capacity according to the applicable product standard and test conditions.

Does MCCB breaking capacity depend on voltage?

Yes. The specified breaking capacity should always be considered together with the applicable rated operating voltage, product model, and manufacturer's technical data.

Is a higher breaking capacity always better?

Not necessarily. The MCCB should have a suitable breaking capacity for the prospective short-circuit current and the requirements of the electrical system. Selection should also consider rated current, voltage, protection characteristics, and coordination requirements.

How do I choose the right breaking capacity for an MCCB?

First determine the system voltage and rated load current, then obtain the prospective short-circuit current at the installation point. Compare these requirements with the MCCB's specified Icu and Ics ratings and confirm the other system requirements.

Conclusion

Breaking capacity is one of the key parameters for evaluating an MCCB's short-circuit protection capability. While rated current describes the normal operating capacity of a circuit breaker, Icu and Ics provide important information about its short-circuit interruption performance. Therefore, selecting an MCCB requires consideration of the complete electrical system rather than relying on rated current alone.

Thank you for reading this guide. We hope this article helps you better understand MCCB breaking capacity and make more informed decisions when selecting low-voltage circuit protection equipment. For more information about our MCCBs and other low-voltage electrical products, please visit https://www.chboko.com/to explore our product range and contact our team for further technical information.