RM6-12 Ring Main Unit SF6 Gas-Insulated Switchgear

The RM6-12 Gas-Insulated Switchgear is a fully-insulated, hermetically-sealed SF₆ metal-enclosed ring main unit (RMU) designed for 10kV medium-voltage distribution systems. Certified by the National High-Voltage Apparatus Testing Center and recognized as a Zhejiang High-Tech Product, it excels in reliability, modularity, and environmental adaptability. Widely used in urban/rural power distribution, industrial/commercial facilities, and renewable energy projects, it provides safe, efficient, and maintenance-free power distribution solutions.

    Key Advantages

    Excellent insulation and arc extinguishing performance:

     The RM6 device makes full use of the excellent insulation and arc extinguishing performance of SF6 gas to effectively prevent electrical faults, thereby ensuring the stable operation of the power system.

    Versatile modular design:

     The device is designed with modularity as the core, and electrical components such as circuit breakers, load switches and earthing switches can be customized according to specific needs to provide customized power distribution solutions.

    Space-saving structure:

    Its design focuses on compactness, which can be easily installed and used even in space-constrained environments, thereby optimizing the installation space.

    Easy operation and maintenance:

     The device adopts a front operation design and does not require internal maintenance, which significantly improves the safety and convenience of operation. The simplified maintenance process helps to reduce operating and maintenance costs.

    Environmental management:

     The device adopts an SF6 gas closed-loop system and an environmentally friendly design approach to minimize the impact on the environment. It is also carefully designed for easy recycling and disposal, which meets environmental requirements.

    Comprehensive protection:

     The RM6 device provides a range of protection functions, including overload and short-circuit protection, to ensure that the power grid and connected equipment remain safe and stable under various conditions.

    Product Parameters

    Item

    Unit

    C Module

    (Load Switch)

    F Module

    (Combined Apparatus)

    V Module

    (Vacuum Switch)

    Isolation/

    Earthing Switch

     

    CB Module

    (Vacuum Circuit Breaker)

    Isolation/

    Earthing Switch

     

    Rated Voltage

    KV

    12

    12

    12

    12

    12

    12

    Rated Frequency

    Hz

    50

    50

    50

    50

    50

    50

    Power Frequency Withstand Voltage (PhasetoPhase / Port)

    kV

    42/48

    42/48

    42/48

    42/48

    42/48

    42/48

    Lightning Impulse Withstand Voltage

    kV

    75/85

    75/85

    75/85

    75/85

    75/85

    75/85

    Rated Current

    A

    630

    Note ¹

    630

     

    1250/630

    1450

    Breaking Capability

     

     

     

     

     

     

     

    Rated Loop Breaking Current

    A

    630

     

     

     

     

     

    Rated Cable Charging Breaking Current

    A

    10

     

     

     

     

     

    Rated ShortCircuit Making Current (Peak)

    A

    50

     

     

     

     

     

    Rated Peak Withstand Current

    kA

    50

    80

     

     

     

     

    Rated ShortTime Withstand Current

    kA/35

    20

     

    20

     

     

     

    Rated ShortCircuit Breaking Current

    kA

     

    31.5

    20

     

    25

     

    Rated Transfer Current

    A

     

    1700

     

     

     

     

    Maximum Current of Equipped Fuse

    A

     

    125

     

     

     

     

    Loop Resistance

    μΩ

    ≤ 300

    ≤ 600

     

     

     

     

    Mechanical Life

    Times

    5000

    3000

    5000

    2000

    5000

    5000

    Note ¹:Depends on the current rating of the fuse

     

     

     

     

     

     