RM6-40.5 Ring Main Unit SF6 Gas-Insulated Switchgear
Overview
BKRM6-40.5 metal ring network switchgear (hereinafter referred to as the inflatable cabinet) is suitable for use in three-phase AC 50Hz, rated voltage 40.5kV distribution systems. It is used for breaking and closing load currents, overload currents, overload currents, and short circuits. It can also disconnect capacitive loads such as no-load transformers, overhead lines at a certain distance, cable lines, and capacitor banks. It plays a role in the distribution, control, and protection of electrical energy in the power system.
BKRM6-40.5 adopts a fully sealed structure, and all primary charged components are sealed in a stainless steel welded chamber with a protection level of IP67. A multi circuit ring network switchgear that can adapt to various harsh environmental conditions such as humidity, salt spray, floods, heavy pollution, etc., and has high operational safety and reliability. Widely used in industrial parks, streets, airports, residential areas, bustling commercial centers, etc., it is an ideal equipment for distribution network automation. It is also used for compact box type substations, cable branch boxes, switch stations, wind power stations, subway and tunnel lights.
BKRM6-40.5 has multiple modules that can be combined according to user requirements, providing multiple combination methods to adapt to the vast majority of situations that require ring network units Up to 4 modules can be configured in the same SF6 gas chamber. When there are more than 4 units in the module, an extended busbar can be used to connect the switchgear.
Key Advantages
Fully sealed and insulated design: All live parts of BKRM6-40.5 are sealed in a box made of 304 stainless steel plate welded together. The box is filled with SF6 gas with a working pressure of 1.4 bar and a protection level of IP67. It can be installed in areas with high humidity and dust pollution, especially suitable for mines, box type substations, and any places where surface flashover is easily caused by air pollution. The product is equipped with a DIN47636 standard conduit and connected to the cable through fully insulated, fully sealed, and shielded cable joints.
High reliability and personal safety: All live parts are sealed in SF6 gas chambers; The chamber has a reliable pressure relief channel and has passed an internal fault arc test of 20kA/0.5s; The load switch and grounding switch are three position switches, simplifying the interlocking between them. There is a reliable mechanical interlock between the cable room cover and the load switch, effectively preventing accidental entry into the live interval.
Maintenance free and long lifespan: The product is designed to have a lifespan of 30 years, during which the main switch does not require maintenance. The annual leakage rate of the product is ≤ 0.1%.
Compact structure: Except for the air insulated metering cabinet and PT cabinet, all modules are only 500mm wide The cable connection sleeves of all units have consistent ground height, which facilitates on-site construction.
BKRM6-40.5 can be equipped with intelligent control devices (optional), providing effective protection, remote control, and monitoring systems, and supporting automation of power distribution systems.
BKRM6-40.5 provides two protection methods for transformers: load switch fuse combination and circuit breaker with relay protection. Load switch fuse combination devices are used for transformers of 1600kVA and below, while circuit breakers with relays can be used for transformer protection of various capacities.
Environmental Protection: The development of BKRM6-40.5 includes not only the product itself, but also the environmental protection from the production process to the lifelong operation of the switch. All materials are selected to be environmentally friendly, using zero leakage cleaning technology. The product is sealed for life, and 90% to 95% of the materials can be recycled after the end of the product life cycle.
Product Parameters
|
Item |
Unit |
C Module |
F Module |
V Module |
CB Module |
||
|
(Load Switch) |
(Combined Apparatus) |
(Vacuum Switch) |
Isolation/ |
(Vacuum Circuit Breaker) |
Isolation/ |
||
|
Rated Voltage |
kV |
36/40.5 |
35/40.5 |
36/40.5 |
36/40.5 |
36/40.5 |
36/40.5 |
|
Power Frequency Withstand Voltage |
kV |
70/95 |
70/95 |
70/95 |
70/95 |
70/95 |
70/95 |
|
Isolation Port Voltage |
kV |
80/110 |
80/110 |
80/110 |
|
|
80/110 |
|
Lightning Impulse Withstand Voltage (Isolation Port) |
kV |
170/185 |
170/185 |
170/185 |
170/185 |
170/185 |
170/185 |
|
Isolation Port (kV) |
kV |
195/215 |
|
195/215 |
|
|
195/215 |
|
Rated Current |
A |
630/6301 |
|
200/200 |
|
630/630 |
|
|
Breaking Capability |
|
|
|
|
|
|
|
|
Active Load |
A |
630/6330 |
|
200/200 |
|
|
|
|
Loop Current Breaking |
A |
630/630 |
|
200/200 |
|
|
|
|
NoLoad Cable Charging |
A |
20/21 |
|
20/21 |
|
50(C1) |
|
|
Ground Fault |
A |
60/63 |
|
60/63 |
|
|
|
|
Ground Fault Cable Charging |
A |
35/36 |
|
35/36 |
|
|
|
|
Transfer Current |
A |
|
|
840/750 |
|
|
|
|
ShortCircuit Breaking Current |
kA |
|
|
20(Expected) |
|
20/20[EI,S] |
|
|
Making Capacity |
kA |
50/50 |
|
|
|
|
|
|
(50 Times) |
50/50 |
|
|
|
|
|
|
|
(50 Times) |
50(Expected) |
2.5/2.5 |
|
|
|
|
|
|
(5 Times) |
50/50 |
50/50 |
|
|
|
|
|
|
Class (Electrical Life) |
|
E3/E2 |
E2/E2 |
/ |
E2/E2 |
E2/E2 |
E2/E2 |
|
3s ShortTime Withstand Current |
kA |
20/20 |
20/20 |
Limited by HighVoltage Fuse |
|
20/20 |
20/20 |
|
Internal Arc Classification IAC AFL. 1s |
|
20/20 |
|
20/20 |
|
20/20 |
|