S11 high-performance oil immersed power transformer with fully sealed structure
product advantage
Our company's products use Dyn11 in the connection group, which can significantly reduce the adverse effects of harmonics on the power grid and improve the quality of power supply. Its fully sealed structure is a major highlight. It eliminates the oil storage tank and automatically adjusts the oil volume change through the elasticity of the corrugated oil tank's corrugated sheet, isolating the transformer from air and effectively preventing and slowing down oil degradation and insulation aging, extending its service life. During normal operation, there is no need to hang the core or repair it. In addition, the transformer has excellent short-circuit resistance design, such as using low axial short-circuit force structure coils and high reliability support structure body, greatly improving the ability to withstand short circuits.
Technical parameters
|
Rated Capacity kVA |
Voltage Combination kV |
Connection Symbol |
Loss kW |
No-load Current % |
Short-circuit Impedance % |
Weight kg |
External dimensions(mm) L*B*H |
Track gauge |
||||
|
High Voltage |
Low Voltage |
No-load |
Load |
Equipment Weight |
Oil Weight |
Total Weight |
||||||
|
200 |
10.5 10 6.3 6 |
6.3 3.1 5 3 |
Yd11 Dy11 |
0.34 |
3.15 |
1.8 |
4.5 |
650 |
160 |
1000 |
1180×740×1270 |
660/660 |
|
250 |
0.40 |
3.6 |
1.7 |
770 |
200 |
1190 |
1230×800×1340 |
|||||
|
315 |
0.48 |
4.3 |
1.6 |
900 |
215 |
1300 |
1320×810×1370 |
|||||
|
400 |
0.57 |
5.2 |
1.5 |
1080 |
260 |
1650 |
1380×900×1390 |
|||||
|
500 |
0.68 |
6.2 |
1.4 |
1250 |
280 |
1890 |
1400×920×1450 |
|||||
|
630 |
0.82 |
6.92 |
0.6 |
5.5 |
1470 |
340 |
2245 |
1580×1020×1430 |
820/820 |
|||
|
800 |
1.00 |
8.96 |
0.6 |
1735 |
385 |
2685 |
1665×1070×1520 |
|||||
|
1000 |
1.18 |
9.91 |
0.6 |
1910 |
430 |
2940 |
1740×1160×1550 |
|||||
|
1250 |
1.40 |
11.7 |
0.5 |
2210 |
590 |
3640 |
1820×1210×1740 |
|||||
|
1600 |
1.68 |
14.1 |
0.4 |
2640 |
680 |
4270 |
1940×1240×1860 |
|||||
|
2000 |
2.01 |
16.9 |
0.4 |
2890 |
725 |
4775 |
2210×1920×1970 |
|||||
|
2500 |
2.37 |
19.6 |
0.4 |
3460 |
910 |
5710 |
2260×1970×1995 |
1070/1070 |
||||
|
3150 |
2.80 |
23.3 |
0.4 |
4230 |
1350 |
7085 |
2320×2280×2360 |
|||||
|
4000 |
10.5 |
6.3 3.1 5 |
3.45 |
27.3 |
0.4 |
5025 |
1675 |
8150 |
2640×2480×2475 |
|||
|
5000 |
4.10 |
31.3 |
0.4 |
6020 |
1940 |
9610 |
2575×2640×2590 |
|||||
|
6300 |
4.89 |
35 |
0.4 |
8125 |
2550 |
12660 |
2640×2820×2810 |
|||||
|
8000 |
6.52 |
40.5 |
0 |
9620 |
2780 |
15100 |
2710×2840×3040 |
1475/1475 |
||||
|
10000 |
7.70 |
47.70 |
0.55 |
11660 |
3070 |
17480 |
2850×2880×3265 |
|||||
Note: ① High voltage tap range: * 5% or * 2 * 2.5%; Frequency 50Hz
The provided external dimensions are for reference only during selection, and the final dimensions are subject to the product's external drawing
Normal use contiditons
Altitude: not exceeding 1000m;
Environmental temperature: maximum temperature+40 ℃;
The average temperature of the hottest month is+30 ℃;
The highest annual average temperature is+20 ℃;
The minimum outdoor temperature is -25 ℃.
The waveform of the power supply voltage is approximately a sine wave
For three-phase transformers, the three-phase power supply voltage should be roughly symmetrical
Installation environment: There is no obvious pollution in the installation environment;
Ground acceleration caused by earthquakes: horizontal direction less than 3m/s', vertical direction less than 1.5m/s
Special usage conditions
Any special usage conditions beyond the normal usage conditions of the transformer should be specified during the inquiry and ordering process.
Execution Standards
GB/T1094.1 GB/T1094.2 GB/T1094.3 GB/T1094.5
GB/T25289 GB/T6451 GB/T7595 GB20052
JB/T3837 JB/T10088
The transformer products produced by our company meet the latest version of the above standards.
Ordering Instructions
When placing an order, the product model, rated capacity, high and low voltage ratings, high voltage division range, number of phases, frequency, and connection group number should be provided.