SVG (Static Var Generator)
Overview
SVG (Static Var Generator), also known as Static Synchronous Compensator (STATCOM), is an advanced dynamic reactive power compensation device. It rapidly outputs or absorbs reactive power by regulating the output of the bridge - type circuit. With fast response and precise compensation capabilities, it can improve the power factor, stabilize voltage, and enhance power quality. It is widely applied in power systems and industrial scenarios.
Product Features
It has an extremely fast response speed and can track and compensate for the reactive power changes in the system within milliseconds.
With high compensation accuracy, it can achieve continuous and stepless adjustment, precisely control the reactive power output, and stabilize the system voltage and power factor.
It supports the bidirectional regulation of capacitive and inductive reactive power, flexibly adapting to various complex working conditions.
Some SVGs have the function of harmonic suppression, which can optimize the power quality.
It adopts a modular design, making it convenient for capacity expansion, inspection, and maintenance.
It has high conversion efficiency, low self - loss, and remarkable energy - saving effect.
Product Parameters
| Capacity (kVar) | 35 | 50 | 75 | 100 |
| Grid Voltage | 380V (-40%~+20%) | 380V (-40%~+20%) | 380V (-40%~+20%) | 380V (-40%~+20%) |
| Grid Frequency | 45Hz - 62Hz | 45Hz - 62Hz | 45Hz - 62Hz | 45Hz - 62Hz |
| Grid System | 3 - phase 4 - wire / 3 - phase 3 - wire | 3 - phase 4 - wire / 3 - phase 3 - wire | 3 - phase 4 - wire / 3 - phase 3 - wire | 3 - phase 4 - wire / 3 - phase 3 - wire |
| Efficiency | ≥ 97.5% | ≥ 97.5% | ≥ 97.5% | ≥ 97.5% |
| Rated Compensation Capacity | 35kVar | 50kVar | 75kVar | 100kVar |
| Target Power Factor | Adjustable from -1 to +1 | Adjustable from -1 to +1 | Adjustable from -1 to +1 | Adjustable from -1 to +1 |
| Fast Response Time | < 50us | < 50us | < 50us | < 50us |
| Total Response Time | < 5ms | < 5ms | < 5ms | < 5ms |
| Filter Function | ASVG supports compensation for low - order (3rd, 5th, 7th, 9th, 11th harmonics) | ASVG supports compensation for low - order (3rd, 5th, 7th, 9th, 11th harmonics) | ASVG supports compensation for low - order (3rd, 5th, 7th, 9th, 11th harmonics) | ASVG supports compensation for low - order (3rd, 5th, 7th, 9th, 11th harmonics) |
| Protection Functions | Grid under - voltage protection, short - circuit protection, over - compensation protection, IGBT over - temperature protection, etc. | Grid under - voltage protection, short - circuit protection, over - compensation protection, IGBT over - temperature protection, etc. | Grid under - voltage protection, short - circuit protection, over - compensation protection, IGBT over - temperature protection, etc. | Grid under - voltage protection, short - circuit protection, over - compensation protection, IGBT over - temperature protection, etc. |
| Communication Interface | RS485 | RS485 | RS485 | RS485 |
| Communication Protocol | Modbus Protocol | Modbus Protocol | Modbus Protocol | Modbus Protocol |
| User Interface | HMI (4.3 - inch) | HMI (4.3 - inch) | HMI (4.3 - inch) | HMI (4.3 - inch) |
| Installation Method | Rack - mount | Rack - mount | Rack - mount | Rack - mount |
| Dimensions | 456×575×200mm | 456×575×232mm | 456×575×232mm | 456×575×270mm |
| Weight | 37Kg | 40Kg | 45Kg | 48Kg |
| Cooling Method | Intelligent Air Cooling | Intelligent Air Cooling | Intelligent Air Cooling | Intelligent Air Cooling |
| Ambient Temperature | -25~+45℃ | -25~+45℃ | -25~+45℃ | -25~+45℃ |
Capacity Calculation SVG
The capacity S of BKASVG is jointly determined by the reactive power capacity Q1 required by the system and the harmonic capacity Q2.
S=Q12+Q22 (and S≥2Qh) (Formula 5)
When the harmonic content is relatively small, the capacity of SVG can be approximately obtained by taking an appropriate margin from the reactive power capacity. If the harmonic content is relatively large, it must be calculated through Formula 5.
Calculation of Reactive Power Compensation Capacity
The reactive power compensation capacity is usually selected as 30% of the system capacity.