ZW32 Series Outdoor Three Phase Medium Voltage Vacuum Circuit Breaker
Overview
ZW32-12 outdoor high voltage vacuum circuit breaker (hereinafter referred to as circuit breaker) is outdoor distribution equipment with rated voltage of 12kV and three-phase AC of 50Hz. It is mainly used to open and close load current, overload current and short circuit current in power system. It is suitable for the protection and control in the power distribution system of substation and industrial and mining enterprises, as well as the places where the rural power grid is frequently operated. The circuit breaker has the characteristics of small volume, lightweight, anti-condensation, free maintenance and so on. It can adapt to the harsh weather conditions and a dirty environments.
Model and Meaning

Working Conditons
1.The environment temperature: upper limit +40C. lower linit-30℃
2.Altitude s 2000 meters
3.Wind pressure: no more than 700Pa (corresponding to the wind speed 34m/s)
4.Earthquake intensity: do not exceed 8 degree
5.Pollution grade: I class
6.Maximum daily temperature: less than 25℃.
Technical parameters
| Name | Unit | Data | ||
| Rated Voltage | kV | 12 | ||
| Rated Insulation Level | 1min Power Frequency Withstand Voltage | Dry Test (To Ground, Pole-to-Pole / Break) | 42/48 | |
| Wet Test | 34 | |||
| Lightning Impulse Withstand Voltage (Peak Value, Pole-to-Pole / Break) | 75/85 | |||
| Rated Current | A | 630 | ||
| Rated Short-Circuit Breaking Current | kA | 20 | ||
| Rated operating sequence | O~0.3-CO-180S-COS | |||
| Rated short-circuit breaking current breaking times | Times | 30 | ||
| Rated Short-Circuit Making Current (Peak Value) | kA | 50 | ||
| Rated Peak Withstand Current | ||||
| Rated Short-Time Withstand Current | 20 | |||
| Rated Short-Circuit Duration time | S | 4 | ||
| Opening Time | ms | ≤35 | ||
| Closing Time | ms | ≤40 | ||
| Mechanical Life | Times | 10000 | ||
| Rated Closing Operation Voltage | V | DC110 | ||
| Rated Opening Operation Voltage | ||||
| Overcurrent Protection | Current Setting Multiple | 0.2~2.5 | ||
| Allowable deviation of setting current | ±10% | |||
| Delay Setting Value | S | 0~5 | ||
| Delay Tolerance | ±10% | |||
| Instantaneous Trip Protection | Current Setting Multiple | 2.5~10 | ||
| Allowable deviation of setting current | ±10% | |||
| Delay Setting Value | S | 0~0.5 | ||
| Delay Tolerance | ±10% | |||
| AC Charging Input Current of Control Unit | Rated Value | A | 5 | |
| Fluctuation Range | 0.5~8 | |||
PRODUCT SIZE DESCRIPTION