Leave Your Message
Products Categories
Featured Products

ZW32 Series Outdoor Three Phase Medium Voltage Vacuum Circuit Breaker

ZW32-12 outdoor high voltage vacuum circuit breaker (hereinafter referred to as circuit breaker) is outdoor distribution equipment with rated voltage of 12kV and three-phase AC of 50Hz. It is mainly used to open and close load current, overload current and short circuit current in power system. It is suitable for the protection and control in the power distribution system of substation and industrial and mining enterprises, as well as the places where the rural power grid is frequently operated. The circuit breaker has the characteristics of small volume,  lightweight, anti-condensation, free maintenance and so on. It can adapt to the harsh weather conditions and a dirty environments.

    Overview

    ZW32-12 outdoor high voltage vacuum circuit breaker (hereinafter referred to as circuit breaker) is outdoor distribution equipment with rated voltage of 12kV and three-phase AC of 50Hz. It is mainly used to open and close load current, overload current and short circuit current in power system. It is suitable for the protection and control in the power distribution system of substation and industrial and mining enterprises, as well as the places where the rural power grid is frequently operated. The circuit breaker has the characteristics of small volume,  lightweight, anti-condensation, free maintenance and so on. It can adapt to the harsh weather conditions and a dirty environments.

    Model and Meaning

    1.1.ZW32 Series Outdoor Three Phase Medium Voltage Vacuum Circuit Breaker.png

    Working Conditons

    1.The environment temperature: upper limit +40C. lower linit-30℃

    2.Altitude s 2000 meters

    3.Wind pressure: no more than 700Pa (corresponding to the wind speed 34m/s)       

    4.Earthquake intensity: do not exceed 8 degree

    5.Pollution grade: I class

    6.Maximum daily temperature: less than 25℃.

    Technical parameters

    Name Unit Data
    Rated Voltage kV 12
    Rated Insulation Level 1min Power Frequency Withstand Voltage Dry Test (To Ground, Pole-to-Pole / Break) 42/48
    Wet Test 34
    Lightning Impulse Withstand Voltage (Peak Value, Pole-to-Pole / Break) 75/85
    Rated Current A 630
    Rated Short-Circuit Breaking Current kA 20
    Rated operating sequence O~0.3-CO-180S-COS
    Rated short-circuit breaking current breaking times Times 30
    Rated Short-Circuit Making Current (Peak Value) kA 50
    Rated Peak Withstand Current
    Rated Short-Time Withstand Current 20
    Rated Short-Circuit Duration time S 4
    Opening Time ms ≤35
    Closing Time ms ≤40
    Mechanical Life Times 10000
    Rated Closing Operation Voltage V DC110
    Rated Opening Operation Voltage
    Overcurrent Protection Current Setting Multiple 0.2~2.5
    Allowable deviation of setting current ±10%
    Delay Setting Value S 0~5
    Delay Tolerance ±10%
    Instantaneous Trip Protection Current Setting Multiple 2.5~10
    Allowable deviation of setting current ±10%
    Delay Setting Value S 0~0.5
    Delay Tolerance ±10%
    AC Charging Input Current of Control Unit Rated Value A 5
    Fluctuation Range 0.5~8

    PRODUCT SIZE DESCRIPTION

    1.2.ZW32 Series Outdoor Three Phase Medium Voltage Vacuum Circuit Breaker.png1.3.ZW32 Series Outdoor Three Phase Medium Voltage Vacuum Circuit Breaker.png

    Leave Your Message